System Operation, Testing and Maintenance
Replacing the Humidifier Canister
! CAUTION
Risk of contact with extremely hot surfaces. Can cause injury.
Canister and steam hose may be hot. Do not attempt to replace parts until the humidifier has cooled down to a temperature that is safe for human contact. Use extreme caution and wear thermally insulated gloves and arm protection when replacing the humidifier canister.
The proper procedure to replace the humidifier canister is:
1.Turn off the humidifier by lowering the humidity setpoint below the ambient humidity level. Record the original setpoint.
2.Place the RUN/DRAIN switch in the DRAIN position to drain the water from the canister.
3.Return the RUN/DRAIN switch to the RUN position after the canister has drained.
4.Turn OFF the power at the main unit.
5.Remove the cover from the humidifier cabinet.
6.Locate the power wires to the steam canister. They are connected to the canister with 1/4" quick connects. Make note of the wiring configuration before removing any wires. Refer to schematic on unit. Slide the rubber boot back to expose the connections. Remove the two (2) power wires and the
7.Loosen the steam outlet hose clamps and slide the steam hose away from the canister fitting. Release the canister clamp along the base of the canister.
8.Remove the canister.
9.Reverse previous steps to
•When replacing the wiring, connect the red wire from terminal #1 on the interface to the red tip terminal on the canister. Reconnect the power wires as before (#2 on the left and #1 on the right)
•When replacing the canister, always check the fill and drain solenoids for proper operation.
9.3.4Humidifier Circuit Board Adjustments
! WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power disconnect switches before working on the humidifier printed circuit board.
Verify that electric power is Off with a voltmeter prior to the procedure.
The humidifier control board governs humidifier operation. There are three potentiometers mounted on the board and can be used to adjust for extreme water conductivity conditions.
POT2 controls the amperage at which the drain will energize and is clearly marked in percentages. This adjustment is
Lowering the value decreases the frequency of drain cycles.
The frequency should be increased for highly conductive water and decreased for less conductive water. If adjustment is necessary and a change of three to four percent in either direction does not permit normal operation of the unit, consult your Liebert supplier.
The POT1 controls the duration of the drain cycle. This adjustment is
The DIP switch settings are used to set the capacity of the humidifier. If the humidifier is replaced in the field the DIP switches should be set to the required settings described below.
Table 24 Humidifier control board DIP switch settings
Voltage | SW1 | SW2 | SW3 | SW4 | Amps |
208 | On | On | On | Off | 8.9 |
240 | Off | On | On | Off | 8.5 |
380/415 | Off | Off | Off | Off | 5.2 |
460 | On | On | On | Off | 4.5 |
575 | On | On | Off | Off | 3.4 |
Liebert® | 62 |