Emerson MINI-MATE2 user manual Water/Glycol Dimensional Data

Models: MINI-MATE2

1 72
Download 72 pages 34.22 Kb
Page 40
Image 40
WATER/GLYCOL DIMENSIONAL DATA

Site Preparation and Installation

Figure 21 Indoor water/glycol condensing unit dimensional data

NOTE: Unit is evenly spaced in reference to threaded rod centers.

Removable Access Panel

1/2" (12.7mm) dia. holes for module rigging (typ. 2 each end)

32"

(812.8mm)

Cabinet

Dimension

Manual background 32" (812.8mm)

Cabinet

Dimension

Field-supplied threaded rods for module support from ceiling typ. 4).

24"

(610mm) Cabinet Dimension

Hanger

 

Bracket

 

Shaded area indicates a

28"

recommended clearance of

(711mm)

30" (762mm) for component

Threaded Rod

access and removal

Centers

335/8"

(854.1mm)

Threaded Rod

Centers

WATER/GLYCOL DIMENSIONAL DATA

 

7/8" (22.2mm) & 1-1/8" (28.6mm)

 

7/8" (22.2mm) & 1 1/8" (28.6mm)

dia. knockouts electrical entrance for

 

dia. knockouts electrical entrance for

line voltage connection

 

line voltage connection (Single Point

 

8-7/16"

 

 

(214.4mm)

 

Power Kit)

 

 

 

 

 

Suction Line male

 

3-3/4"

7"

 

(95.2mm)

quick connect

 

(177.8mm)

location

 

 

 

Liquid Line

 

1-1/8" (28.6mm) OD CU Water/Glycol

male quick

 

connect location

 

Inlet Connection. Extends

 

 

3-1/2" (88.9mm) beyond panel exterior

 

 

1-1/8" (28.6mm) OD Cu Water/Glycol

 

 

Outlet Connection Extends

7/8" (22.2mm) dia. electrical entrance

3-1/2" (88.9mm) beyond panel exterior

7/8" (22.2mm) dia. knockout

 

for low-voltage connection

 

DPN000227

 

electrical entrance for alternate

 

 

 

 

control panel low-voltage routing.

Rev. 3

Liebert® Mini-Mate2

34

Page 40
Image 40