System Performance Microprocessor Controls
7.2.3Humidification Operation
The canister humidifier is activated when the humidity control calculates a requirement of 100% humidification; and is deactivated when the humidification requirement falls below 50%.
7.3Load Control Features
The control system monitors the compressor and prevents it from turning on within a 3 minute period of being off. If this
7.3.1Communications
The control system uses a
The communications channel provides both monitoring and control options, including:
•TEMPERATURE/HUMIDITY: Current temperature and humidity readings.
•STATUS (%), Cooling/heating and humidify/dehumidify operating status.
•PRESENT ALARMS: Alarms currently activated.
•SET POINTS:
•Temperature Set point
•Temperature Sensitivity
•Humidity Set point
•Humidity Sensitivity
•High Temperature Alarm
•Low Temperature Alarm
•High Humidity Alarm
•Low Humidity Alarm
•ON/OFF STATUS and CONTROL
•SILENCE ALARM