Site Preparation and Installation
5.1.2Location Considerations
! CAUTION
Risk of leaking water/glycol. Can cause equipment, furniture and building damage.
Do not mount units over equipment or furniture that can be damaged by leaking water /glycol. Install a watertight drain pan with a drain connection under the cooling unit and ceiling mounted
NOTE
Do NOT mount units in areas where normal unit operating sound may disturb the working environment.
Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access for routine maintenance or service. Do not attach additional devices (such as smoke detectors, etc.) to the housing, as they could interfere with the maintenance or service.
NOTE
Temperature and humidity sensors are located in the wall box. Carefully select a position for the box where discharge air DOES NOT blow directly on the sensors.
Figure 8 Air-cooled systems
Evaporator | Evaporator |
| |
Prop Fan |
|
Condensing Unit | Centrifugal Fan |
| Condensing Unit |
Split System Evaporator | Split System Evaporator |
Supply & Return Air Ducted | Supply & Return Air Ducted |
Outdoor Prop Fan Condensing Unit | Indoor |