Site Preparation and Installation
Figure 20
Left Air Intake
Guard Height
Top Air Discharge
Right Air
Intake
| Shaded area indicates |
2" | a minimum clearance of |
18" (457mm) for proper | |
(51mm) | air flow |
53" |
| ||
(1346mm) |
| (978) | |
Shaded area indicates |
| Shaded area indicates | |
a minimum clearance of |
| ||
18" (457mm) for proper | Removable front panel | a minimum clearance of | |
air flow | 24" (610mm) for component | ||
for access to | |||
| access and removal | ||
| and | ||
| DPN000131 | ||
| and to refrigeration components | ||
|
| Rev. 0 |
Table 15 Net weight, high ambient and
Model # | Module | ||
|
| Net Weight | |
60Hz | 50Hz | ||
lb. (kg) | |||
|
|
| |
PFH067A- H | PFH066A- H | 488 (222) | |
PFHZ67A- L | |||
|
5.6.2Piping Connections
Details for refrigerant loop piping are in 5.4.3 - Piping Connections and Coolant Requirements.
5.6.3Electrical Connections
Refer 5.4.4 - Electrical Connections for general wiring requirements and cautions. Refer to electrical schematic when making connections.
Power Connections
The outdoor condensing unit requires its own power source and earth ground, with a disconnect switch (field supplied) to isolate the unit for maintenance.
Control Connections
Liebert® | 32 |