Microprocessor Control
6.12Alarm Enable
Each alarm can be disabled or enabled. Use the Up and Down arrows to select a particular alarm, press Enter to select either Enable or Disable. Press Enter again to store the change. When the alarm is disabled it will NOT report to either the wall box beeper or to the common alarm relay.
NOTE
The
6.13Alarm Time Delay
Each individual alarm can be programmed with a time delay, causing the unit to delay a specified amount of time
NOTE
For software alarms such as “loss of power” and “short cycle,” the time delay should be left at the factory default of 0.
Table 19 Alarm default time delays
| Default Time Delay |
Alarm | (seconds) |
Custom Alarm #1 | 0 |
Custom Alarm #2 | 6 |
High Temperature | 30 |
Low Temperature | 30 |
High Humidity | 30 |
Low Humidity | 30 |
Short Cycle | 0 |
Loss of Power | 0 |
6.14Common Alarm Enable
Each individual alarm can be selected to activate or deactivate the common alarm relay. If the energize common alarm function is set to Yes, the relay is energized immediately as the alarm is annunciated and
Liebert® | 44 |