Microprocessor Control
6.9.5Valve Time (for Systems With a Modulating Chilled Water Valve)
This function shows the full valve travel time of the modulating valve on a chilled water system. This is the time it takes for the valve to travel from full closed to full open. It is programmable from 50 to 250 seconds; factory default time is 165 seconds and should not be changed. The full valve travel time is used by the control to determine the appropriate valve position. For example, if the valve travel time is 165 seconds and 50% cooling is being called for, the valve will open for 83 seconds to achieve 50% open.
6.9.6CW Flush (for Systems with a Modulating Chilled Water Valve)
This function shows the interval time at which the system will perform a modulating chilled water valve system flush cycle. The factory default is 24 (hours) and is programmable from 0 (hours) which signifies to never flush, to 99 (hours) which signifies to flush after every 99 hours of valve
Table 18 Setup functions, default values and allowable ranges
Function | Default | Range |
|
|
|
Restart Time | 0.1 | 0 to 9.9 min |
Delay |
| (0 = manual restart) |
C/F Degrees | °F | °C or °F |
|
|
|
Humidity Control | Rel | Relative or Absolute |
|
|
|
Valve Time | 165 | 50 to 250 seconds |
|
|
|
CW Flush | 24 | 0 to 99 hours |
|
|
|
6.10Change Passwords
The display will prompt the operator to enter a three digit password when attempting to make changes. The system includes two (2) passwords, one for setpoints and one for setup. The system allows the password to be changed by first entering the default password set at the factory
6.11Calibrate Sensors
The temperature and humidity sensors can be calibrated by selecting the CALIBRATE SENSORS menu item. The temperature sensor can be calibrated ±5°F, while the humidity sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value shown will always be % RH, even though absolute humidity control may be selected. If absolute humidity control is selected, the Normal Status Display will display the adjusted reading. This reading may not agree with the relative humidity reading displayed while in calibration.
If the sensors are subject to frequent wide temperature and humidity swings, it may be necessary to shorten the cycling by increasing the sensor time delay. If the sensors are located too close to the air discharge, they will likely experience rapid swings in measurement. Another method in reducing compressor cycling is to increase the temperature and/or humidity sensitivity.
43 | Liebert® |