Frymaster Protector Series operation manual Danger, Non-CEStandard for Incoming Gas Pressures

Models: Protector Series

1 66
Download 66 pages 44.54 Kb
Page 12
Image 12
Non-CE Standard

After the fryer has been positioned under the exhaust hood, ensure the following has been accomplished:

1.Adequate means must be provided to limit the movement of fryers without depending upon the gas line connections. If a flexible gas hose is used, a restraining cable must be connected at all times when the fryer is in use. The restraining cable and installation instructions are packed with the flexible hose in the accessories box that was shipped with your unit.

Manual background DANGER

Do not attach an apron drainboard to a single fryer. The fryer may become unstable, tip over, and cause injury. The appliance area must be kept free and clear of combustible material at all times.

2.Level fryers equipped with legs by screwing out the legs approximately 1 inch then adjusting them so that the fryer is level and at the proper height in the exhaust hood. Frymaster recommends that the minimum distance from the flue outlet to the bottom edge of the hood be 24 in. (600 mm) when the appliance consumes more than 120,000 BTU per hour. NOTE: There are no built-in leveling devices on fryers equipped with casters. The floor where the fryer is to be installed must be level.

3.Test the fryer electrical system:

a.Plug the fryer electrical cord(s) into a grounded electrical receptacle.

b.Place the power switch in the ON position. Verify that the display indicates CYCL.

c.Place the fryer power switch in the OFF position. Verify that the display indicates OFF.

4.Refer to the data plate on the inside of the fryer door to determine if the fryer burner is configured for the proper type of gas before connecting the fryer quick-disconnect device or piping from the gas supply line.

5.Verify the minimum and maximum gas supply pressures for the type of gas to be used in accordance with the accompanying tables.

CE Standard

for Incoming Gas Pressures

for Fryers Manufactured After April 1999

 

Pressure

Orifice Diameter

Regulator Pressure

 

 

Single

Dual

Single

Dual

Gas

(mbar)(1)

Vat

Vat

Vat

Vat

G20

20

2 x 3.40

2 x 3.40

7 mbar

7 mbar

 

G25

20 or 25

2 x 3.40

2 x 3.40

10 mbar

10 mbar

 

G30

28/30 or 50

2 x 2.05

2 x 2.05

17 mbar

17 mbar

 

G31

37 or 50

2 x 2.05

2 x 2.05

20 mbar

20 mbar

 

(1) mbar = 10,2 mm H2O

Non-CE Standard

for Incoming Gas Pressures

Gas

Minimum

Maximum

 

6" W.C.

14" W.C.

Natural

1.49 kPa

3.48 kPa

 

14.93 mbar

34.84 mbar

 

11" W.C.

14" W.C.

LP

2.74 kPa

3.48 kPa

 

27.37 mbar

34.84 mbar

 

 

 

 

 

 

6.For fryers equipped with a FootPrint Pro system or basket lifts, plug the electrical cord(s) into a power receptacle behind the fryer.

2-4

Page 12
Image 12
Frymaster Protector Series operation manual Danger, Non-CEStandard for Incoming Gas Pressures