Digital EnergyLP Series

4 - Installation

4.1Transport

NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading capacity. Move the UPS in its original package to the final destination room. Do not stack other package on top.

4.2Unpacking

Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to the pallet. Remove the UPS from the pallet.

BE CAREFUL! Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS from the pallet! Never try to lift the unit by yourself!

The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate measures to avoid damage on vulnerable floors.

4.3Package Contents

The shipping box contains a LP-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.5.3) a safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the carrier and place of purchase immediately.

4.4Location

Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.

4.5Installation

IMPORTANT:

Before making any connection and switching on the LP UPS, please check the following conditions:

The voltage and frequency of your utility supply is 120/208/230/240 Vac and 50 or 60 Hz; from the factory the input and output of the UPS are set to 208 Vac / 60 Hz.

Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the UPS, as well as at the I/O terminals.

Overcurrent protection for the AC circuit is to be provided by others.

CAUTION: To reduce risk of fire, connect only to a circuit input/output provided with branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI / NFPA 70, as indicated below:

 

UPS model

Input overcurrent protection

 

Output overcurrent protection

 

 

 

(Amps)

 

 

 

 

 

 

(Max. Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating input voltage

120V

 

208V

 

240V

 

120V

 

 

120V

 

208V

 

240V

 

 

 

 

 

 

 

(1 X)

 

 

(2X)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LP 5-11U

 

35

 

30

40

 

20

 

25

 

20

 

LP 5-11U /120V

60

 

 

 

 

 

40

 

 

20

 

25

 

20

 

LP 6-11U

 

 

40

 

35

 

50

 

 

25

 

30

 

25

 

LP 6-11U /120V

70

 

 

 

 

 

50

 

 

25

 

30

 

25

 

LP 8-11U

 

 

60

 

45

 

70

 

 

35

 

40

 

35

 

LP 10-11U

 

 

70

 

60

 

80

 

 

40

 

50

 

40

Table 1. external input fuse value

LX: OPM_LPU_11U_5K0_10K_1US_V030

9

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 11