5.3Use

Once the unit is in operation, there is no need to switch the unit on/off during use.

If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7) results in a total absence of the output voltage (also the bypass voltage) of at least 5 secs.

If an emergency shutdown switch has been installed (see 4.5.1.1-2, step 6) the UPS will stop immediately when the switch is opened. Restart is only possible after closing the switch and turning the UPS off and on again with the UPS on/off switch (rear panel, 7).

The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore the UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.

The menus on the display can be divided into 5 groups:

1standard screen

2information menu (5.3.1)

3status- and alarm menu (5.3.2)

4 service menu (5.3.3)

5 set-up menu (5.3.4)

The standard menu shows UPS model and actual load.

LP 5-11U

LOAD 37%

5.3.1 Information Menu

When the default screen is displayed the first information screen can be entered by depressing the 'up' key (front panel, 4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information screens. After the last information screen the default screen will appear.

The screens display the following information:

INPUT LINE 208V

2.45kW 60Hz

OUTPUT 208V LOAD 50% 60.0Hz

BATTERY 23°C

271V 1.9A

AUTONOMY TIME LEFT 5:27:00

OPERATING TIME 0YEAR 29DAYS

Utility voltage and utility frequency, and the power delivered by the utility.

Output voltages and output frequency, and the power delivered by the UPS (as % of the nominal UPS rating).

The temperature near the batteries, the battery voltage and the battery current (charging: + value, discharging: - value).

The remaining battery runtime (or autonomy) during a utility failure.

The total operating time of the UPS.

LX: OPM_LPU_11U_5K0_10K_1US_V030

25

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 27
Image 27