GE LP11U user manual LP 5/6/8/10-11U installation drawings

Models: LP11U

1 48
Download 48 pages 57.82 Kb
Page 46
Image 46

g

Digital EnergyLP Series

LP 5/6/8/10-11U installation drawings

Model

 

 

Heat dissipation

 

 

 

 

Dimensions

 

Weight

 

Air flow

 

Amb.

 

Rel.

Altitude

 

 

Input wiring

 

 

Output wiring

 

 

 

 

Linear load 240 Volt

 

 

 

 

 

 

 

 

 

 

 

100%

 

temp.

 

humidity

(max 4000m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load

 

 

non-cond.

 

 

 

 

 

 

 

 

 

 

 

 

100% load

 

 

 

50% load

 

h

 

w

 

d

 

 

 

 

 

 

 

 

 

 

 

 

utility volt.

utility volt.

utility volt.

output

output

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120V

208V

240V

volt. 120V

volt. 208V

volt. 240V

LP-U

 

W

Btu/hr

 

W

 

Btu/hr

 

Inch

 

Inch

 

Inch

 

Lbs

 

 

m3/hr

 

°F

 

 

 

m

AWG/mm2

AWG/mm2

AWG/mm2

AWG/mm2

AWG/mm2

AWG/mm2

5-11

571

1950

 

 

389

 

1329

 

26.8

 

12.3

 

28.7

295

 

660

14-104

<95

<1000, derating

 

N.A.

10/6

10/6

8/10

10/6

10/6

6-11

661

2254

 

 

381

 

1300

 

26.8

 

12.3

 

28.7

295

 

660

14-104

<95

12.5% per 1000

 

N.A.

8/10

10/6

8/10

10/6

10/6

8-11

948

3234

 

 

551

 

1882

 

26.8

 

12.3

 

28.7

386

 

660

14-104

<95

 

 

 

 

N.A.

6/14

8/10

6/14

8/10

8/10

10-11

1090

3719

 

 

556

 

1896

 

26.8

 

12.3

 

28.7

410

 

660

14-104

<95

 

 

 

 

N.A.

4/22

6/14

4/22

8/10

8/10

5-11/120 V

641

2187

 

 

425

 

1451

 

39.2

 

12.3

 

28.7

386

 

660

14-104

<95

 

 

 

6/14

N.A.

N.A.

8/10

10/6

10/6

6-11/120 V

744

2539

 

 

601

 

2051

 

39.2

 

12.3

 

28.7

386

 

660

14-104

<95

 

 

 

4/22

N.A.

N.A.

8/10

10/6

10/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

Minimum free space required

 

Distance between mounting

 

Input overcurrent protection

 

Output overcurrent protection (AMPS)

 

 

 

 

 

 

 

 

 

(Inches)

 

 

 

holes (Inches)

 

 

(AMPS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

front

side

 

rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LP-U

 

 

 

 

 

 

 

 

 

 

 

 

x

 

y

 

z

 

120V

 

208V

 

240V

 

120V

120V

 

208V

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1 X)

(2X)

 

 

 

 

 

 

 

 

 

5-11

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

 

 

 

35

 

30

 

40

20

 

25

 

20

 

 

 

 

 

5-11 /120V

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

60

 

 

 

 

 

 

40

20

 

25

 

20

 

 

 

 

 

6-11

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

 

 

 

40

 

35

 

50

25

 

30

 

25

 

 

 

 

 

6-11 /120V

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

70

 

 

 

 

 

 

50

25

 

30

 

25

 

 

 

 

 

8-11

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

 

 

 

60

 

45

 

70

35

 

40

 

35

 

 

 

 

 

10-11

 

4

 

 

2

 

 

8

 

 

7.24

22.76

 

7.48

 

 

 

 

70

 

60

 

80

40

 

50

 

40

 

 

 

 

 