g

Digital EnergyLP Series

UPS Type

:

5-11U

6-11U

8-11U

10-11U

ENCLOSURE

 

 

 

 

 

Sheet steel cubicle

:

VSD2

VSD2

VSD2

VSD2

Colour front

:

RAL 9006 (aluminum)

 

 

Colour cabinet

:

RAL 9010 (white)

 

 

Protection

:

IP 20

 

 

 

Dimensions (hxwxd, mm)

:

680x313x730

680x313x730

680x313x730

680x313x730

Dimensions (hxwxd, inch)

:

26.8x12.3x28.7 26.8x12.3x28.7

26.8x12.3x28.7

26.8x12.3x28.7

(height with castors)

 

 

 

 

 

Weight (with batteries, Kg)

:

134 kg

134 kg

175 kg

186 kg

Weight (with batteries, Lbs)

:

295 Lbs

295 Lbs

386 Lbs

410 Lbs

GENERAL DESIGN CRITERIA

 

 

 

 

 

Mechanical

:

IP20

 

 

 

Humidity

:

95% non condensing

 

 

Safety

: UL 1778; 2001, C-UL

 

 

 

 

EN 50091-1-1: 1999; EN 60950 / IEC 950: 2001

 

Surge capability

: 6kV 1.2/50µs; 3kA 8/20µs

 

 

EMC

: FCC part 15, class A; EN 50091-2

 

 

ENVIRONMENT

 

 

 

 

 

Ambient temperature

: -10 to +40°C (14 to 104°F)

 

 

Audible noise at 1 meter

:

40 - 50dB(A),

 

 

 

 

 

the audible noise is load and temperature dependent

 

LX: OPM_LPU_11U_5K0_10K_1US_V030

42

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 44
Image 44
GE LP11U user manual Enclosure