g

TSTAMP Q4

6028773 1

FREQ RANGE: 2%

NO LOAD : 1

QUICK BATTERY TEST PRESS ENTER

CALIBRATE BAT PRESS DOWN+ENTER

PF1 THYRISTOR 1 BATT.THYRISTOR 0

VSS THYRISTOR 0 PF1. CONVERTER 1

BAT CHARGER

2

INVERTER

1

 

 

LAST TEST TIME 0:00:00

FORCE BYPASS press DOWN+ENTER

AUTOMATIC BYPASS

ENABLED

BATTERY 7Ah BAT. CHARGE 86%

PLL LOCK SPEED

NORMAL

ECO DISABLED ENTER/RESET CHNG

AUTO RESTART ON ENTER/RESET CHNG

Digital EnergyLP Series

Service information on internal timer.

Frequency tracking range: output converter frequency will follow the bypass frequency within these limits before returning to its own internal frequency. Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%. See 5.3.4 Set-up Menu.

No-load shutdown: after a 10 minutes delay the UPS will shut down during utility failure if the load is < 2%. It will restart after the utility returns or when the unit is switched off and on again.

Default setting = 1 (active). For disabling this feature see 5.3.4.

Start of the manual Quick Battery Test.

See for more information section 5.4.2 'Quick Battery Test'

Start of the manual Deep Battery Calibration Test.

See for more information sections 5.4.3 'Deep Battery Calibration Test'

Service information on internal UPS components

Service information on internal UPS components

Service information on internal UPS components

Batt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging, 4 = maintenance charge

Duration of latest test performed, hh/mm/ss

The UPS transfers the load to bypass when the keys 'down' (2) and 'Enter/Reset' (3) on the front panel are depressed simultaneously for approx. 1 second. If the bypass supply is not within limits, the lower line will show the text 'UNAVAILABLE'.

Service set-up information whether the bypass is enabled (default) or disabled. If disabled: UPS will NOT go to bypass. For disabling the bypass refer to the set-up menu (5.3.4).

Service set-up information about the total battery capacity. Information about the actual battery charge condition. For changing the programmed battery capacity refer to the set-up menu (5.3.4).

Service set-up information about frequency tracking speed for the inverter to follow the bypass frequency, LOW (1Hz/sec.) is the normal value and default. HIGH (5Hz/sec.) may be suitable if the UPS is connected to a generator with fast frequency changes and the UPS must be synchronized to prevent alarms. For changing the lock speed refer to the set-up menu (5.3.4).

Service set-up information about the ECO-mode. By pressing ‘Enter/Reset’ the ECO-mode can be enabled or disabled, depending on the actual status. In this way the load will be supplied by way of the electronic bypass. If the ECO-mode is disabled the load will be supplied by the inverter. See also 5.5.5.

Service set-up information about the autorestart function. This function can be switched on or off by pressing ‘Enter/Reset’, depending on the actual status. See also 4.5.6.

LX: OPM_LPU_11U_5K0_10K_1US_V030

29

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 31
Image 31
GE LP11U user manual Tstamp Q4, Automatic Bypass Enabled