UPS Type

 

:

5-11U

 

6-11U

8-11U

10-11U

Output power (kVA/kW)

 

:

5/4

 

6/4.8

8/6.4

10/8

AC input voltage

 

: 120/208/240 Vac (120V only with step-up transformer for LP 5/6-11U)

Input frequency

 

:

60/50 Hz

 

 

 

AC output voltage

 

:

120/208/220/230/240V

 

 

Output frequency

 

: 60 or 50 Hz, std. 60 Hz; selectable on front

System efficiency (full load)

 

:

87%

 

 

 

 

Line input breaker (C-type)

 

:

32A

 

32A

50A

63A

Bypass input breaker (C-type)

 

:

32A

 

32A

50A

63A

Battery safety fuse (F4A)

 

:

30A

 

30A

30A

30A

Battery safety fuse (F4B)

 

:

30A (spare)

30A (spare)

30A

30A

Internal safety fuse (F5A)

 

:

-

 

-

30A

30A

Internal safety fuse (F5B)

 

:

30A

 

30A

30A

30A

Input/output connectors

 

: terminals at rear of unit

 

 

INPUT

 

 

 

 

 

 

 

 

AC input voltage range (208V-240V)

 

 

 

 

 

 

 

at 100% load

 

:

162 - 285 V

 

 

 

at

50% load

 

:

146 - 285 V

 

 

 

at

20% load

 

:

133 - 285 V

 

 

 

AC input voltage range (120V, L5/6-11U)

 

 

 

 

 

 

at 100% load

 

:

81 - 141 V

 

 

 

at

50% load

 

:

72 - 141 V

 

 

 

at

20% load

 

:

66 - 141 V

 

 

 

Input frequency range

 

:

40-70 Hz

 

 

 

Input current wave form

 

:

sinusoidal

 

 

 

Input power factor

 

:

0.99

 

 

 

 

Max. input current at 100% load

120V

:

43.3A

 

50.8A

n.a.

n.a.

 

 

208V

:

25.0A

 

30.0A

40.5

50.3

 

 

240V

:

21.4A

 

25.1

34.8

42.0

Inrush current

 

:

none

 

 

 

 

Rectified DC voltage out

 

:

380 V

 

 

 

 

BATTERY CHARGER

 

 

 

 

 

 

 

Characteristic

 

:

U/I-characteristic, constant

current

charging until boost/float voltage, then

 

 

 

 

constant voltage charging and boost charge mode for fast recharging of

 

 

 

 

batteries

 

 

 

DC input voltage range

 

:

350-450 V

 

 

 

DC output voltage at 20 °C

 

:

float: 273 V

boost: 295 V

 

 

Output current limit (Adc)

 

:

2.0

 

2.0

3.0

3.0

OUTPUT CONVERTER

 

 

 

 

 

 

 

Output power at pf. = 0.8, VA*

 

:

5000

 

6000

8000

10000

Semiconductor

 

:

IGBT

 

 

 

 

AC output voltage

 

: 120/208/240V ± 1% static resistive load

 

 

 

 

120/208/240V ± 2% measured crest load 2.5:1

 

 

 

 

120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of

 

 

 

 

rated load applied or removed

 

Typical overload

 

:

110%

20 minutes

 

 

(temp. dependent)

 

 

130%

3.5 minutes

 

 

 

 

 

 

150%

2 minutes

 

 

Output frequency

 

: 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility

Freq. tracking range

 

: ± 2/4/6% of nominal, user selectable

 

Output wave form

 

:

sine wave

 

 

 

Max. phase difference input-output

 

:

max 7°

 

 

 

 

Harmonic distortion

 

: 2% max. with linear load

 

 

Power factor range

 

:

Any lagging or leading power factor permitted within the specified rating to

 

 

 

 

pf. 0.5

 

 

 

 

Output derating altitude

 

: Till 1000m no derating

 

 

 

 

 

 

Above 1000m 12.5% per 1000m, max. 4000m

Protection

 

: Automatic shut down (or transfer to bypass, if bypass is available) in case of

-low/high DC voltage

-overtemperature

-overload / short circuit

The output is protected against connection to the utility supply * according to EN 50091-1