4.5.6 LP 11U series: 2 / 3 / 4 parallel operating units – additional info

The RPA option (Redundant Parallel Architecture) allows you to create a redundant UPS system in which 2, 3 or 4 LP-U units operate in parallel. The following should be considered when installing units in parallel.

This section gives aditional information on:

-installation (4.5.6.1)

-start-up (4.5.6.2)

-use / maintenance (4.5.6.3)

4.5.6.1Notes concerning installation of a parallel system

1.All inputs of the UPSs must be supplied from the same phase. This is to enable bypass operation of the parallel system. All inputs must be individually protected by fuses in the installation. The values of these fuses should correspond to the values mentioned in section 4.5 table 1.

2.All outputs must be connected together, supplying the load. It is advised to install switches (S 1-4, fig. 17) in the output wiring, in order to be able to isolate a unit from the remaining system for service and maintenance purposes. It is advised to make a Neutral-to-Ground bounding in the output junction.

3.The diameter of input and output cables must be according to the table in the installation drawings (see appendix). Cables with different diameters can cause tripping fuses in the UPS and/or the installation.

4.The length of all input cables from the input junction (Li, fig. 17) to the UPS inputs should be equal. The same applies to the cables from the outputs to the output junction (Lo, fig. 17). The minimum length of the input as well as the output cables is 3 meters / 10 feet.

1-PHASE 3-WIRE INPUT

INPUT JUNCTION

F1-4

DISTRIBUTION FUSE VALUES ACCORDING TO TABLE 1

BUS

TERMINATOR

IN

IN

 

IN

 

IN

LP-UPS

LP-UPS

 

LP-UPS

 

LP-UPS

 

 

 

 

 

 

 

RPA CARD

 

RPA CARD

 

RPA CARD

 

RPA CARD

OUT

OUT

 

OUT

 

OUT

S 1-4

SWITCH ALLOWS

ISOLATION OF A UNIT

FROM THE SYSTEM

 

 

OUTPUT JUNCTION

Li/Lo: LENGTH OF I/O WIRING

MAKE

YELLOW NETWORK

- EQUAL FOR EACH UPS

NEUTRAL-TO-GROUND

CABLES AS DELIVERED

- MINIMUM 3 METERS / 9.8 FEET

BOUNDING HERE

WITH THE UPS

 

 

TO LOAD

BUS

TERMINATOR

Figure 17. Installation of parallel operating LP-U UPSs

LX: OPM_LPU_11U_5K0_10K_1US_V030

19

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 21
Image 21
GE LP11U user manual Installation of parallel operating LP-U UPSs