INPUT AND OUTPUT NOT SYNCHRONIZED

Digital EnergyLP Series

The output converter frequency is not synchronized to the utility (input) frequency. In this situation the automatic bypass switch is not able to transfer the load from output converter to bypass and reverse: automatic bypass operation is inhibited: if for whatever reason the output converter is unable to deliver the required output, output power is lost. (see section 3.5).

Synchronization is only possible if the utility frequency remains within certain limits (see chapter 10).

BATTERY RUNTIME LEFT 0:09:41

OUTPUT OFF

NO INPUT POWER

PROG. SHUTDOWN WITHIN 0:09:17

PROG. SHUTDOWN LEFT 0:14:03

SHUTDOWN ALARM PRESS UP

IMMEDIATE

SHUTDOWN

5.3.3 Service Menu

The remaining runtime. This figure is counted down during battery operation until either the utility returns or the batteries are depleted.

The output is switched off due to a faulty situation, indicated by the second line.

The output will be switched off by a remote command (RS232/SNMP). The second line indicates the time until shutdown.

The output is switched off by a remote command (RS232/SNMP). The second line indicates the time until wake-up.

The output is switched off by the 'no-load shutdown' feature: no input voltage and load <2%. If the input voltage is restored, the output will be available again. See also section 5.5.1

The wire on connector J3 pin 3-4 (rear panel, plug-in card 12) is interrupted. The output is no longer available. To restart the unit, restore the connection and turn the on/off switch (rear panel, 7) off and on again.

When the default screen is displayed you can enter the first service screen by depressing the keys 'down' (2) and 'Enter/Reset' (3) simultaneously for approx. 1 second. Using the 'up' (4) and 'down' (2) keys you can scroll through several service screens.

SERVICE SCREENS

ENTER exit

SERIAL NUMBER l051U01/0020A030

SOFTWARE VERSION R2.9; 640777

FAN SPEED

10

INV.DC: +

375

 

 

HEATSI.TEMP: 0

TRANSF.TEMP: 310

FLOAT CHARGE: 1

OUTPUT FAST : 0

The intro service screen. 'Enter/Reset' returns to the default screen.

The serial number of the UPS.

Release number of the installed software and production code of the UPS.

Service information about fan speed (min. 10, max. 30) and internal DC voltage.

Service information on internal temperature levels, values in mV over the temperature sensors.

First line: service information on charger. ‘1’ = batteries have reached float voltage.

Second line: service information on output converter.

LX: OPM_LPU_11U_5K0_10K_1US_V030