INPUT AND OUTPUT NOT SYNCHRONIZED
Digital Energy™ LP Series
The output converter frequency is not synchronized to the utility (input) frequency. In this situation the automatic bypass switch is not able to transfer the load from output converter to bypass and reverse: automatic bypass operation is inhibited: if for whatever reason the output converter is unable to deliver the required output, output power is lost. (see section 3.5).
Synchronization is only possible if the utility frequency remains within certain limits (see chapter 10).
BATTERY RUNTIME LEFT 0:09:41
OUTPUT OFF
NO INPUT POWER
PROG. SHUTDOWN WITHIN 0:09:17
PROG. SHUTDOWN LEFT 0:14:03
SHUTDOWN ALARM PRESS UP
IMMEDIATE
SHUTDOWN
5.3.3 Service Menu
The remaining runtime. This figure is counted down during battery operation until either the utility returns or the batteries are depleted.
The output is switched off due to a faulty situation, indicated by the second line.
The output will be switched off by a remote command (RS232/SNMP). The second line indicates the time until shutdown.
The output is switched off by a remote command (RS232/SNMP). The second line indicates the time until
The output is switched off by the
The wire on connector J3 pin
When the default screen is displayed you can enter the first service screen by depressing the keys 'down' (2) and 'Enter/Reset' (3) simultaneously for approx. 1 second. Using the 'up' (4) and 'down' (2) keys you can scroll through several service screens.
SERVICE SCREENS
ENTER exit
SERIAL NUMBER l051U01/0020A030
SOFTWARE VERSION R2.9; 640777
FAN SPEED | 10 |
INV.DC: + | 375 |
|
|
HEATSI.TEMP: 0
TRANSF.TEMP: 310
FLOAT CHARGE: 1
OUTPUT FAST : 0
The intro service screen. 'Enter/Reset' returns to the default screen.
The serial number of the UPS.
Release number of the installed software and production code of the UPS.
Service information about fan speed (min. 10, max. 30) and internal DC voltage.
Service information on internal temperature levels, values in mV over the temperature sensors.
First line: service information on charger. ‘1’ = batteries have reached float voltage.
Second line: service information on output converter.
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 28 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |