GE LP11U user manual Test Screens, Automatic Bypass Enabled Service Warning Disabled

Models: LP11U

1 48
Download 48 pages 57.82 Kb
Page 33
Image 33
TEST ACTIVATED
TEST SUCCESSFUL TEST FAILED NOT AVAILABLE

g

AUTOMATIC BYPASS

ENABLED

SERVICE WARNING

DISABLED

Digital EnergyLP Series

Controls functioning of the automatic bypass switch. Range: ENABLED/DISABLED. If the UPS is used as a frequency converter you may change the setting to ‘DISABLED’. Bypass operation will then be inhibited and all alarms related to ‘bypass out of limits’ are suppressed.

The system can prompt for service to a user defined schedule.

Range: 8/12/16/20/24/28 months or DISABLED. To reset the timer: first select “DISABLED” and subsequently set a new alarm interval.

5.4Test Screens

These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS monitoring software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.

Upper lines:

second line:

 

GENERAL SYSTEM

TEST START

the test will start soon

QUICK BATTERY

TEST ACTIVATED

the test is running

CALIBRATE BAT

TEST SUCCESFUL

the test has been completed succesfully

BYPASS

TEST FAILED

the test has not been completed succesfully

5.4.1 Battery Test, general

Automatic test: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the batteries and the wiring are able to support power failures. The tests do not cause any interruption in the functioning of the unit.

Manual test: A manual battery test can be activated

-either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of your interface package), or

-via the front panel: see below

5.4.2Quick Battery Test

From the standard menu first enter the service menu (press the 'down' and 'Enter/Reset' keys simultaneously, then press the 'down' key until the following screen appears:

QUICK BATTERY

TEST PRESS ENTER

The ‘Enter/Reset’ key confirms the selection, and the screen shows:

QUICK BATTERY

TEST START

The test status (indicated by the second line) can be:

= testing

= battery has been tested with positive result

= the batteries should be replaced

= battery capacity too low to start the test

If the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will be generated. The batteries must be replaced as soon as possible (see section 8.3).

NOTE: If the manual test is started immediately after installation or after a power failure, the UPS may generate a false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during the power failure.

LX: OPM_LPU_11U_5K0_10K_1US_V030

31

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 33
Image 33
GE LP11U user manual Test Screens, Automatic Bypass Enabled Service Warning Disabled, Quick Battery Test Start