g

Digital EnergyLP Series

5.The right option slot (14) at the rear of the unit contains the the RPA-card. Before the parallel system can be put into operation a unique number has to be appointed to each UPS in the system. This can be 0, 1,

2 or 3. Start with 0 for the first unit, 1 for the second, 2 for the third and 3 for the last unit:

-loosen the screws, remove the RPA-card

-set the dipswitch to the appointed number (fig. 18)

-re-install the RPA-card, fasten the screws.

Do NOT install the network cables between the RPA-cards of the units yet!

Figure 18. Appointing a unique number to each UPS in the system

6.In the UPS many parameters can be set. It is advised to keep the same setting for each parameter in each UPS in the parallel system. In any case the following parameters are critical and should have equal settings:

-autorestart (on/off, see 5.3.3)

-output voltage (120/208/220/230/240 Vac, see 5.3.4)

-output frequency (50/60 Hz, see 5.3.4)

It is absolutely required that these parameters are set to the same value. Off factory this is the case. If you’re not sure that the units have equal settings:

-be sure that the RPA-cards of the units have not been interconnected yet

-be sure that utility power is connected to the UPS

-start each unit individually (see 5.2), check / change the parameters, and switch the unit off again.

7.Interconnect the RPA-cards of the units, using the network cable that came with the UPS. See figure 17 (dotted line). Only install the cables that were delivered with the UPSs! Of the first and the last UPS in the system only one RPA-socket is used to interconnect the UPSs. A bus terminator must be placed in the other (free) RPA-socket. The required bus terminators have been delivered with the unit.

4.5.6.2 Notes concerning starting up the parallel system

For starting up the system please refer to section 5.2.

After switching on all units the LP UPSs will show the following display:

AUTORESTART OFF

PRESS ENTER

After pressing the ‘Enter/Reset’ button on one of the units the system will start up. All units will display the standard screen. The number in the lower right corner indicates the number of the UPS in the system.

LP 5-11U

 

LOAD 40%

2

If the parameters mentioned in 4.5.6.1 step 6 are not set to the same value the UPS will display the following screen after start-up:

AUTORESTART OFF

SETTING MISMATCH

In this case check and correct the setting of the parameters as mentioned in 4.5.6.1, step 6.

LX: OPM_LPU_11U_5K0_10K_1US_V030

20

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Page 22
Image 22
GE LP11U user manual Autorestart OFF Press Enter, Autorestart OFF Setting Mismatch