FAN SPECIFICATIONS
Fan and Heater
3450 RPM Vane Axial Fan
FAN HORSEPOWER |
| 3/4 |
|
|
| 1 |
|
| 1.1/2 |
|
|
| 3 |
| |||
RPM |
| 3450 |
|
| 3450 |
|
| 3450 |
|
| 3450 |
| |||||
PHASE | 1 |
| 3 |
| 1 |
| 3 |
| 1 |
| 3 |
| 1 |
| 3 |
| |
VOLTS | 230 | 230 | 460 | 575 | 230 | 230 | 460 | 575 | 230 | 230 | 460 | 575 | 230 | 230 |
| 460 | 575 |
FULL LOAD AMPS | 5.5 | 2.6 | 1.3 | 1.0 | 5.5 | 3.0 | 1.5 | 1.2 | 7.5 | 4.6 | 2.3 | 1.8 | 1 5 | 7.4 |
| 3.7 | 3 |
MINIMUM WIRE SIZE | Copper Wire | Copper Wire | Copper Wire | Copper Wire | |||||||||||||
50' RUN | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 2 | 1 2 |
| 1 4 | 1 4 |
100' RUN | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 2 | 1 4 | 1 4 | 1 4 | 1 0 | 1 2 |
| 1 2 | 1 2 |
200' RUN | 1 2 | 1 4 | 1 4 | 1 4 | 1 2 | 1 4 | 1 4 | 1 4 | 8 | 1 2 | 1 4 | 1 4 | 8 | 1 0 |
| 1 2 | 1 2 |
300' RUN | 1 0 | 1 4 | 1 4 | 1 4 | 1 0 | 1 4 | 1 4 | 1 4 | 6 | 1 0 | 1 2 | 1 2 | 6 | 8 |
| 1 0 | 1 0 |
MINIMUM WIRE SIZE | Aluminum Wire | Aluminum Wire | Aluminum Wire | Aluminum Wire | |||||||||||||
50' RUN | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 2 | 1 2 | 1 4 | 1 4 | 1 2 | 1 2 |
| 1 2 | 1 2 |
100' RUN | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 4 | 1 0 | 1 2 | 1 2 | 1 4 | 8 | 1 0 |
| 1 2 | 1 2 |
200' RUN | 1 0 | 1 4 | 1 4 | 1 4 | 1 0 | 1 4 | 1 4 | 1 4 | 6 | 1 0 | 1 2 | 1 2 | 6 | 1 0 |
| 1 0 | 1 0 |
300' RUN | 8 | 1 2 | 1 4 | 1 4 | 8 | 1 2 | 1 4 | 1 4 | 4 | 1 0 | 1 2 | 1 2 | 4 | 8 |
| 1 0 | 1 0 |
FUSE SIZE (SLOW BLOW) | 1 5 | 1 0 | 5 | 5 | 1 5 | 1 0 | 5 | 5 | 1 5 | 1 0 | 5 | 5 | 3 0 | 1 5 |
| 1 0 | 1 0 |
BREAKER SIZE | 2 0 | 1 5 | 1 0 | 1 0 | 2 0 | 1 5 | 1 0 | 1 0 | 2 0 | 1 5 | 1 0 | 1 0 | 4 0 | 2 0 |
| 1 5 | 1 5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FAN HORSEPOWER |
|
|
| 7 |
|
| 10 |
|
| 15 |
| |||
RPM |
| 3450 |
|
| 3450 |
|
| 3450 |
| |||||
PHASE | 1 |
|
| 3 |
| 1 |
| 3 |
| 1 |
| 3 |
| |
|
|
|
|
|
|
| ||||||||
VOLTS | 230 |
| 230 |
| 460 | 575 | 230 | 230 | 460 | 575 | 230 | 230 | 460 | 575 |
FULL LOAD AMPS | 3 0 | 1 8 |
| 9 | 6.9 | 4 7 | 2 5 | 1 3 | 9.6 | 5 7 | 3 2 | 1 6 | 1 4 | |
MINIMUM WIRE SIZE |
| Copper Wire | Copper Wire | Copper Wire | ||||||||||
50' RUN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 0 |
| 1 0 |
| 1 2 | 1 2 | 8 | 8 | 1 2 | 1 2 | 6 | 6 | 1 0 | 1 0 | |
100' RUN | 8 |
| 1 0 |
| 1 2 | 1 2 | 6 | 6 | 1 0 | 1 2 | 4 | 4 | 1 0 | 1 0 |
200' RUN | 4 |
| 8 |
| 1 0 | 1 2 | 4 | 4 | 1 0 | 1 0 | 2 | 2 | 1 0 | 1 0 |
300' RUN | 4 |
| 6 |
| 8 | 1 0 | 2 | 2 | 8 | 8 | 0 | 0 | 8 | 1 0 |
MINIMUM WIRE SIZE | Aluminum Wire | Aluminum Wire | Aluminum Wire | |||||||||||
50' RUN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
| 8 |
| 1 2 | 1 2 | 6 | 6 | 1 2 | 1 2 | 4 | 4 | 8 | 8 | |
100' RUN | 6 |
| 8 |
| 1 0 | 1 2 | 4 | 4 | 1 0 | 1 0 | 2 | 2 | 8 | 8 |
200' RUN | 3 |
| 6 |
| 1 0 | 1 0 | 2 | 2 | 8 | 1 0 | 0 | 0 | 6 | 8 |
300' RUN | 2 |
| 4 |
| 8 | 1 0 | 0 | 0 | 6 | 8 | 0 0 | 0 0 | 4 | 6 |
FUSE SIZE (SLOW BLOW) | 4 0 |
| 2 5 |
| 1 5 | 1 5 | 6 0 | 3 0 | 2 0 | 1 5 | 7 5 | 4 0 | 2 0 | 2 0 |
BREAKER SIZE | 6 0 |
| 3 0 |
| 1 5 | 1 5 | 8 0 | 4 0 | 2 0 | 2 0 | 100 | 6 0 | 3 0 | 2 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10