GSI Outdoors PNEG-377 Limit Switches, Multiple Heater Error Conditions, Misc Error Numbers

Models: PNEG-377

1 98
Download 98 pages 21.15 Kb
Page 47
Image 47
ERROR CONDITIONS

Fan and Heater

ERROR CONDITIONS

 

 

Limit Switches

The following limit switch errors light up individually on the heaters LCD screen: PLENUM, HOUSING, VAPOR, TEMP HI LIMIT.

Note: When a shutdown does occur due to an error condition, the amount of time elapsed since the shutdown can be viewed by pressing the down arrow switch (up to 218 Hours).

Multiple Heater Error Conditions

If two or more heaters are connected together through the serial link, and the master cannot communicate with a slave controller, the master will display

Misc Error Numbers

"SLA" on the main display

and the "RX" "TX" symbols will be flashing.

If a limit switch error or one of the error numbers 1 through 8 occurs, that error is displayed on the slave where the error originates. The master displays "SLA ERROR".

1

Temperature probe 1 open.

7

Illegal flame sense .

Error 7 is

most likely caused by stuck open solenoid. Error 7 will not shutdown fan until loss of flame is detected by control.

13

+11 volt DC shorted to ground.

2

Temperature probe 1 short.

8

Flame probe short error.

000

This indicates that one of the other on screen errors (vapor, plenum or housing temp hi- limit or flame out or no airflow has occurred).

3

 

 

4

 

 

5

 

6

 

 

 

 

 

 

 

 

 

Temperature

 

Temperature

 

Airflow open.

 

Airflow short.

probe 2 open.

 

probe 2 short.

 

 

 

 

 

 

 

 

 

 

9

 

 

10

 

 

11

 

12

 

 

 

 

 

 

 

 

 

Slave #1 incon-

 

Slave #2

 

Slave #3

 

Wrong voltage.

sistent with mas-

 

inconsistent.

 

inconsistent.

 

Dip switch

ter with either

 

Same as

 

Same as

 

#5 is the voltage

the drying grain

 

error 9 for slave

 

error 9 for slave

 

selector switch.

flag or the LP

#1.

 

#1.

 

If dip switch #5

main solenoid or

 

 

 

 

 

 

in "ON" that se-

cycle solenoid.

 

 

 

 

 

 

lects 240 VAC.

Most likely

 

 

 

 

 

 

If the unit has

the slave got re-

 

 

 

 

 

 

only 120 VAC

set powering up

 

 

 

 

 

 

applied, error 12

with the sole-

 

 

 

 

 

 

will show up. If

noids off.

 

 

 

 

 

 

dip switch #5 is

 

 

 

 

 

 

 

 

"OFF" that se-

 

 

 

 

 

 

 

 

lects 120 VAC. If

 

 

 

 

 

 

 

 

the unit has 240

(Errors 9 through 11 are displayed only if multiple heaters

 

VAC applied er-

 

ror 12 will show

are tied together through serial link).

 

 

 

 

 

 

up.

 

 

 

 

 

 

 

 

Note: Temperature sensor connection-the temperature

 

This is im-

sensor (bolt) must always be connected to the master.

 

portant because

 

 

 

 

 

 

 

 

if the fan heater

 

 

 

 

 

 

 

 

is set up at GSI

 

 

 

 

 

 

 

 

for 120 VAC and

 

 

 

 

 

 

 

 

the customer

 

 

 

 

 

 

 

 

connects to 240

 

 

 

 

 

 

 

 

VAC the heater

 

 

 

 

 

 

 

 

control will work,

 

 

 

 

 

 

 

 

but if allowed to

The heater

control display

showing error #7.

operate the so-

lenoids will

have 240 VAC

applied to them

which will dam-

age solenoids.

47

Page 47
Image 47
GSI Outdoors PNEG-377 service manual Limit Switches, Multiple Heater Error Conditions, Misc Error Numbers