FACTORY CONFIGURATION

FACTORY CONFIGURATION

Fan and Heater

 

 

Configuration Dip

Switches (Normally Done

Multiple heaters connected together through the serial link.

At GSI)

These switches are used to config- ure the heater control for various types of heaters.

Stand alone heater with no slaves, all dip switches in the off state.

Dip switch number 3 by-passes air pressure switch when turned on.

This switch should only be used while trouble-shooting heater. Never leave Heater running with air pressure switch by- passed.

Master with one slave-dip switch 7 on/all others off.

Master with two slaves-dip switch 8 on/all others off.

Master with 3 slaves-dip switch 7

&8 on/all others off.

Slave #1-dip switch one and three on/all others off.

Slave #2-dip switch two and three on/all others off.

Slave #3-dip switch one, two and three on/all others off.

The backside of the control board, showing the dip switch placement.