Hampton Direct H35-LP1 Installation, H1 H, Horizontal Venting with Two 2 90o Elbows, Option

Models: H35-NG1 H35-LP1

1 48
Download 48 pages 46.67 Kb
Page 15
Image 15
Horizontal Venting with Two (2) 90o Elbows

INSTALLATION

Horizontal Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

Option

 

V

H + H1

A)

3'

Min.

2' Max.

B)

4'

Min.

3' Max.

C)

5'

Min.

4' Max.

D)

6'

Min.

5' Max.

E)

7'

Min.

6' Max.

F)

8'

Min.

8' Max.

 

 

 

 

With these options, maxi- mum total pipe length is 30 feet with minimum of 8 feet total vertical and maximum 8 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

H1

Lengths do not include elbow indicated

V

H

Vent restrictor position A (fully open), refer to the "Vent Restrictor Position" section.

Horizontal Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

Option

H

V

H + H1 With these options, max.

A)1' Max. 2' Min. 3' Max. total pipe length is 30 feet with min. of 9 feet total

B)2' Max. 3' Min. 5' Max. vertical and max. 8 feet

C)3' Max. 5' Min. 6' Max. total horizontal.

D)4' Max. 7' Min. 7' Max. Please note min. 1 foot

E)5' Max. 9' Min. 8' Max. betweenrequired.90o elbows is

Lengths do not include elbow indicated

Vent restrictor position A (fully open), refer to the "Vent

Restrcitor Postion" section.

H1

H

V

Hampton® H35 Direct Vent Freestanding Gas Stove

15

Page 15
Image 15
Hampton Direct H35-LP1, H35-NG1 Installation, H1 H, Horizontal Venting with Two 2 90o Elbows, Option, H + H1