VENTING COMPONENTS & CONFIGURATION
The Champlain cannot be vented jointly with any other solid fuel or gas appliance. It must be vented directly to the outside of the building using a proper termination as listed in the manual. Your Champlain Direct Vent stove is approved for use with Simpson
Caution: Make sure all stove and termination cap clearances have been observed per the Owner’s Manual.
Caution: Be sure there is no wiring or plumbing in the chosen location.
Caution: Venting terminals shall not be recessed into a wall or siding.
Note: If further direction is needed for installation, please refer to the venting instructions, which are provided with the venting system.
ACCEPTABLE DIRECT VENT
TERMINATION CAP LOCATIONS
The vent/air intake termination clearances above the high side of an angled roof are as follows:
Roof Pitch | Feet | Meters |
Flat to 6/12 | 1 | 0.3 |
7/12 to 9/12 | 2 | 0.6 |
10/12 to 12/12 | 4 | 1.2 |
13/12 to 16/12 | 6 | 1.8 |
17/12 to 21/12 | 8 | 2.4 |
|
|
|
Listed below are components acceptable for installation. The venting system must be comprised of the appropriate venting components as specified.
APPROVED VENTING SYSTEM COMPONENTS
*Component Description
90 0 Elbow
45 0 Elbow
6" Straight
9" Straight
12" Straight
24" Straight
36" Straight
48" Straight
Vertical Vent Cap Snorkel 36”
Vinyl Siding Standoff 4 x 6 5/8” Round Ceiling Support Wall
Thimble Covers Wall thimble