B. Check Appliance Draft

B. Check Appliance Draft

Check draft of appliance to verify proper venting conditions.

Close all windows and doors, turn on all exhaust fans in home.

Appliance is to be completely assembled to normal operating condition.

Turn on appliance and allow to operate for at least 10 minutes.

Check draft as shown in Figure 13.1. This can be done using a smoke or fl ame producing match.

Hold lit match at bottom edge of draft hood opening and observe fl ame/smoke per the fi gure.

Flame up-Acceptable Flame up-Acceptable

Flame in-Good

Flame in-Good

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flame out-Bad

Flame out-Bad

Without

With doors

doors.

closed.

Figure 13.1 Checking Appliance Draft

C. High Limit Safety Switch

A high limit switch has been installed on this appliance. This switch automatically turns off the appliance if it becomes too hot. If this happens, do not attempt to operate the appliance until it has been examined by a qualifi ed service technician. For the high limit switch location, see Figures 13.2-13.4.

Note to Qualified Service Technician:

The intermittent pilot ignition version of the Geneva Series requires that the limit switch be manually reset if it has shut the appliance off. This is done by fi rst removing the hood to expose the high limit switch. See Figure 28. Push the red button in until you hear a click. The appliance should now be operable. Replace the hood.

Figure 13.2 Remove the Hood

Figure 13.4 Limit Switch Location

Figure 13.5 Resetting the Limit Switch