7 Vent Information and Diagrams

7 Vent Information and Diagrams

A. Approved Pipe

This appliance is approved for use with Hearth & Home Technologies SLP venting systems. Refer to Section 16B for vent component information.

DO NOT mix pipe, fittings or joining methods from differ- ent manufacturers.

The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.

WARNING! Risk of Fire or Asphyxiation. This appli- ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS ter- mination caps are not approved for use with propane (LP) fuel. May lead to elevated glass temperature that may cause tempered glass breakage.

B. Vent Table Key

The abbreviations listed in this vent table key are used in the vent diagrams.

Symbol

Description

 

 

V1

First section (closest to appliance) of vertical length

 

 

V2

Second section of vertical length

 

 

H1

First section (closest to appliance) of horizontal length

 

 

H2

Subsequent sections of horizontal length

 

 

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as- pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).

Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216

mm)horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).

Vertical

in.1/2

-8

8-1/2 in.

A. Approved Pipe Horizontal B. Vent Table Key

Figure 7.1

D. Measuring Standards

Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.

Pipe measurements are shown using the effective length of pipe (see Figure 7.2).

Measurements are made from the appliance outer wrap, not from the standoffs.

Horizontal terminations are measured to the outside mounting surface (flange of termination cap).

Vertical terminations are measured to bottom of termination cap.

Horizontal pipe installed level with no rise.

A C. Use of Elbows

B

1-1/4 in. (32 mm)

OVERLAP

Figure 7.2 Chimney Offset/Return

 

Effective Height/Length

 

Pipe

inches

mm

 

SLP4

4

102

Effective

SLP6

6

152

SLP12

12

305

Height/

SLP24

24

610

Length

SLP36

36

914

 

 

SLP48

48

1219

 

SLP6A

2 - 6

51 - 152

 

SLP12A

2 - 12

51 - 305

Figure 7.3 SLP Pipe Effective Length

E. Vent Diagrams

General Rules:

When penetrating a combustible wall, a wall shield firestop must be installed.

When penetrating a combustible ceiling, a ceiling firestop must be installed.

Horizontal runs of vent do not require vertical rise; horizontal runs may be level.

24

Heatilator • RAVE4013I-C2293-900 Rev. C • 8/12

Page 24