Heatiator Rave4013i-c owner manual Vent Clearances and Framing, Pipe Clearances to Combustibles

Models: Rave4013i-c

1 70
Download 70 pages 45.48 Kb
Page 35
Image 35

8 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:

Between ceiling firestops

Between wall shield firestops

Around vent system

Failure to keep insulation or other material away from vent pipe may cause over heating and fire.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

‡SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to 194 mm thick).

‡,f wall thickness is less than 4-3/8 the e[isting heat shields must be field trimmed. ,f wall thickness is greater than 7-5/8 in. a '9P-HSM-B will be reTuired.

B. Wall Penetration Framing

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration.

The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.

SLP pipe - A wall shield firestop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained.

See Section 10.K for information for regarding the in- stallation of a horizontal termination cap.

Non-Combustible Wall Penetration

3 in. (76 mm) top clearance

1 in. (25 mm) clearance around vertical sections

(SLP Pipe Shown)

 

Heat

3 in. (76 mm)

Shield

top clearance *

 

Heat

 

Shield

 

1 in. (25 mm)

Wall

clearance

Shield

bottom & sides

Firestop

 

WALL

 

If the hole being penetrated is surrounded by noncom- bustible materials such as concrete, a hole with diameter one in. greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.

DO NOT PACK WITH

INSULATION OR

OTHER MATERIAL

* When using SLP pipe, minimum clearances from the vent pipe to combustible materi-

als at inside wall firestops are:Top: 2-1/2 in. (64 mm) Bottom: 1/2 in. (13 mm) Sides: 1 in. (25 mm)

Figure 8.1 Horizontal Venting Clearances To Combustible Materials

10 in.

A

10 in.

B

A*

B

48-1/16 in.

47-1/16 in.

*Shows center of vent framing hole for top venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.

Figure 8.2 Wall Penetration

Heatilator • RAVE4013I-C2293-900 Rev. C • 8/12

35

Page 35
Image 35
Heatiator Rave4013i-c owner manual Vent Clearances and Framing, Pipe Clearances to Combustibles, Wall Penetration Framing

Rave4013i-c specifications

The Heatiator Rave4013i-c stands out as an exceptional heating solution designed to provide efficient, reliable warmth while elevating the aesthetic appeal of any space. This advanced model offers a blend of innovative technology, high performance, and user-friendly features.

One of the most notable characteristics of the Rave4013i-c is its cutting-edge air distribution system. This ensures uniform heat distribution throughout the room, eliminating cold spots and providing consistent warmth. The unit's powerful heat output makes it suitable for various environments, including residential homes, offices, and commercial spaces.

The Rave4013i-c is equipped with energy-efficient technologies that reduce power consumption while maintaining optimal performance. With an impressive heating capacity, the unit is designed to heat larger spaces effectively without incurring steep energy costs. Users appreciate its eco-friendly design, which aligns with today's sustainability goals, helping to lower carbon footprints.

Another significant feature is the sophisticated digital control panel, which allows users to customize their heating experience. The intuitive interface provides easy access to various settings, including temperature adjustments, timer functions, and mode selection. This level of control ensures that users can achieve their desired comfort level with minimal hassle.

The Heatiator Rave4013i-c also boasts an aesthetically pleasing design, incorporating sleek lines and a modern finish that complements any decor. The charming appearance does not compromise its robustness; it is built from high-quality materials that promise durability and long-lasting performance.

Safety is a top priority for the Rave4013i-c. It includes essential safety features such as overheat protection and tip-over switches. These integrated safety measures provide peace of mind, especially in homes with pets and small children. Additionally, its low noise operation allows for peaceful enjoyment of the warmth generated, without disruptive sounds.

Versatility is another hallmark of the Rave4013i-c. It can be installed in various configurations, whether flush-mounted in a wall or standing independently, making it adaptable to different room layouts. This flexibility, combined with its heating efficiency and modern design, makes the Heatiator Rave4013i-c an ideal choice for anyone seeking a high-quality heating appliance that enhances both comfort and style.