Heatiator Rave4013i-c H2 H1 V1, Venting with 3 elbows, Top Vent - Horizontal Termination, 3 ft

Models: Rave4013i-c

1 70
Download 70 pages 45.48 Kb
Page 28
Image 28
Venting with 3 elbows

1. Top Vent - Horizontal Termination - (continued)

Top Vent - Horizontal Termination

Venting with 3 elbows

V Minimum

 

H1 + H2 + H3 MAXIMUM

 

RAVE4013I-C (NG ONLY)

 

 

 

 

3 ft.

 

914 mm

 

15 ft.

4.6 m

 

 

 

 

 

 

 

H1

+ H2 + H3
MAX. = 15 ft. (4.6 m)

 

 

 

V1 MAX. = 7 ft (2.1 m)

 

Note: Use SLP Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS termination caps are not approved for use with pro- pane (LP) fuel. May lead to elevated glass temper- ature that may cause tempered glass breakage.

INSTALLED

HORIZONTALLY

H2

H1

V1

INSTALLED

HORIZONTALLY

H3H1 + H2 + H3 MAXIMUM

Figure 7.7

28

Heatilator • RAVE4013I-C2293-900 Rev. C • 8/12