Heatiator Rave4013i-c Top Vent - Horizontal Termination - continued, Venting with 2 elbows, 1 ft

Models: Rave4013i-c

1 70
Download 70 pages 45.48 Kb
Page 26
Image 26
1. Top Vent - Horizontal Termination - (continued)

1. Top Vent - Horizontal Termination - (continued)

Top Vent - Horizontal Termination

Venting with 2 elbows

 

V Minimum

H1 + H2 MAXIMUM

 

RAVE4013I-C

 

 

 

 

90° Elbow

1 ft.

305 mm

 

 

 

 

 

1 ft.

 

305 mm

2 ft.

610 mm

 

 

 

 

 

2 ft.

 

610 mm

4 ft.

1.2 m

 

 

 

 

 

3 ft.

 

914 mm

6 ft.

1.8 m

 

 

 

 

 

4 ft.

 

1.2 m

15 ft.

4.6 m

 

 

 

 

 

H1 + H2 MAX. =15 ft. (4.6 m)
V + H1 + H2 MAX. = 40 ft. (12.2 m)

Note: Use SLP Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS termination caps are not approved for use with pro- pane (LP) fuel. May lead to elevated glass temper- ature that may cause tempered glass breakage.

H2

H1

INSTALLED

HORIZONTALLY

V1

Figure 7.5

26

Heatilator • RAVE4013I-C2293-900 Rev. C • 8/12

Page 26
Image 26
Heatiator Rave4013i-c Top Vent - Horizontal Termination - continued, Venting with 2 elbows, Installed Horizontally, 305 mm