Heatiator Rave4013i-c Top Vent - Horizontal Termination - continued, Venting with 3 elbows

Models: Rave4013i-c

1 70
Download 70 pages 45.48 Kb
Page 27
Image 27
Top Vent - Horizontal Termination

1. Top Vent - Horizontal Termination - (continued)

 

 

 

 

Top Vent - Horizontal Termination

 

 

 

 

 

 

Venting with 3 elbows

 

 

 

 

 

 

 

 

 

 

 

 

 

RAVE4013I-C

 

 

 

V1 Minimum

H1 + H2 Maximum

 

V2

V1 + V2 Minimum

 

90° Elbow

6 ft.

 

1.8 m

 

*

*

 

1 ft.

305 mm

10 ft.

 

3.0 m

 

*

*

 

2 ft.

610 mm

12 ft.

 

3.7 m

 

*

*

 

3 ft.

914 mm

14 ft.

 

4.3 m

 

*

*

 

 

 

H1

+ H2 MAX. =14 ft. (4.3 m)

 

 

 

 

V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m)

 

 

*No specific restrictions on this value EXCEPT V1 + V2 + H cannot exceed 40 ft. (12.2 m)

 

Note: Use SLP Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS termination caps are not approved for use with pro- pane (LP) fuel. May lead to elevated glass temper- ature that may cause tempered glass breakage.

H2

V2

H1

V1

Figure 7.6

Heatilator • RAVE4013I-C2293-900 Rev. C • 8/12