B. LED Lights and Audible Alarm Safeties
The "POWER" LED indicates proper control voltage and will remain on unless a control voltage problem occurs. For further details, see "II. Sequence of Operation and Service Diagnosis."
Icemaking Sequence
Sequence Step | LED | Energized |
|
|
|
|
| ||
Components |
| Min. | Max. | ||||||
|
|
|
|
| |||||
Fill Cycle |
| WTRIN | WV |
| - |
| On until UFS closes. Alarm sounds | ||
|
|
|
|
|
|
|
| after 90 sec. |
|
Ice Purge Cycle | GM | GM, FM |
| 5 min. |
| 5 min. |
| ||
Freeze Cycle |
| GM, WTRIN* (refill), | GM, Comp, |
| - |
| *On until UFS closes. Alarm | ||
(with refill) |
| COMP | FM, WV* |
|
|
| sounds after 90 sec. | ||
|
|
|
| (refill) |
|
|
|
|
|
Drain Cycle |
| FLUSH (Drain) | DV |
| 2 sec. |
| 10 min. |
| |
|
|
|
| Dispensing Sequence |
|
| |||
Sequence Step | LED | Energized |
| Time LEDs are on | **Dispense Mode Switch | ||||
Components |
| Continuous | Portion | ||||||
Ice Dispense |
| ICE, AM* | IDS**, IDM**, | *AM energizes | 60 sec. per | Adjustable | |||
Activation |
|
| AM* |
| .6 sec. every 12 | activation | between 0.2 sec. | ||
|
|
|
|
|
| sec. of cumulative |
| and 20 sec. | |
|
|
|
|
|
| dispense time |
|
| |
Dispense Water | WTRDP | DispWV |
|
|
|
|
| ||
Valve Activation |
|
|
|
|
|
|
|
| |
The | alarm safeties shut down the appliance. |
|
| ||||||
No. of Beeps |
|
| Type of Alarm |
|
| Reset Options | |||
(every 5 sec.) |
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |
1 |
| Low Water Safety |
|
|
| Automatic reset once water supply is restored | |||
|
| UFS open > 90 seconds after WV energized. | and UFS closes. |
| |||||
2 |
| Control Switch |
|
|
| Automatic reset once the control switch is | |||
|
| In "DRAIN" position longer than 15 minutes. | moved to the "ICE" position. |
| |||||
3 |
|
|
|
| Automatic reset once pressure drops | ||||
|
| First and second activation in 1 hour. |
| below the high pressure threshold and the | |||||
|
|
|
|
|
|
| high‑pressure switch closes. |
| |
4 |
|
|
|
| Call for service. To avoid possible catastrophic | ||||
|
| Third activation in 1 hour. |
| failure, it is recommended to leave the | |||||
|
|
|
|
|
|
| appliance off until this alarm is resolved. | ||
|
|
|
|
|
|
| Manual reset. Turn power off and on again. | ||
5 |
| Freeze Timer |
|
|
| Manual reset. Turn power off and on again. | |||
|
| WV off > 30 minutes since last WV activation. |
|
|
| ||||
6 |
| Low Voltage |
|
|
| "POWER OK" LED turns off if voltage | |||
|
| (92Vac ±5% or less) |
|
|
| protection operates. |
| ||
7 |
| High Voltage |
|
|
| The control voltage safeties automatically | |||
|
| (147Vac ±5% or more) |
| reset when voltage is corrected. | |||||
8 |
| Gear Motor |
|
|
| Manual reset. Turn power off and on again. | |||
|
| GMPR contacts fail to close. |
|
|
|
| |||
9 |
| Infrared Sensor (S1 dip switch 7) |
| Manual reset. Turn power off and on again. | |||||
|
| (Not used on this model) |
|
|
|
|
Legend:
35