B. LED Lights and Audible Alarm Safeties

The "POWER" LED indicates proper control voltage and will remain on unless a control voltage problem occurs. For further details, see "II. Sequence of Operation and Service Diagnosis."

Icemaking Sequence

Sequence Step

LED

Energized

 

 

 

 

 

Components

 

Min.

Max.

 

 

 

 

 

Fill Cycle

 

WTRIN

WV

 

-

 

On until UFS closes. Alarm sounds

 

 

 

 

 

 

 

 

after 90 sec.

 

Ice Purge Cycle

GM

GM, FM

 

5 min.

 

5 min.

 

Freeze Cycle

 

GM, WTRIN* (refill),

GM, Comp,

 

-

 

*On until UFS closes. Alarm

(with refill)

 

COMP

FM, WV*

 

 

 

sounds after 90 sec.

 

 

 

 

(refill)

 

 

 

 

 

Drain Cycle

 

FLUSH (Drain)

DV

 

2 sec.

 

10 min.

 

 

 

 

 

Dispensing Sequence

 

 

Sequence Step

LED

Energized

 

Time LEDs are on

**Dispense Mode Switch

Components

 

Continuous

Portion

Ice Dispense

 

ICE, AM*

IDS**, IDM**,

*AM energizes

60 sec. per

Adjustable

Activation

 

 

AM*

 

.6 sec. every 12

activation

between 0.2 sec.

 

 

 

 

 

 

sec. of cumulative

 

and 20 sec.

 

 

 

 

 

 

dispense time

 

 

Dispense Water

WTRDP

DispWV

 

 

 

 

 

Valve Activation

 

 

 

 

 

 

 

 

The built-in

alarm safeties shut down the appliance.

 

 

No. of Beeps

 

 

Type of Alarm

 

 

Reset Options

(every 5 sec.)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Low Water Safety

 

 

 

Automatic reset once water supply is restored

 

 

UFS open > 90 seconds after WV energized.

and UFS closes.

 

2

 

Control Switch

 

 

 

Automatic reset once the control switch is

 

 

In "DRAIN" position longer than 15 minutes.

moved to the "ICE" position.

 

3

 

High-Pressure Switch

 

 

 

Automatic reset once pressure drops

 

 

First and second activation in 1 hour.

 

below the high pressure threshold and the

 

 

 

 

 

 

 

highpressure switch closes.

 

4

 

High-Pressure Switch

 

 

 

Call for service. To avoid possible catastrophic

 

 

Third activation in 1 hour.

 

failure, it is recommended to leave the

 

 

 

 

 

 

 

appliance off until this alarm is resolved.

 

 

 

 

 

 

 

Manual reset. Turn power off and on again.

5

 

Freeze Timer

 

 

 

Manual reset. Turn power off and on again.

 

 

WV off > 30 minutes since last WV activation.

 

 

 

6

 

Low Voltage

 

 

 

"POWER OK" LED turns off if voltage

 

 

(92Vac ±5% or less)

 

 

 

protection operates.

 

7

 

High Voltage

 

 

 

The control voltage safeties automatically

 

 

(147Vac ±5% or more)

 

reset when voltage is corrected.

8

 

Gear Motor

 

 

 

Manual reset. Turn power off and on again.

 

 

GMPR contacts fail to close.

 

 

 

 

9

 

Infrared Sensor (S1 dip switch 7)

 

Manual reset. Turn power off and on again.

 

 

(Not used on this model)

 

 

 

 

Legend: AM–agitating motors, Comp–compressor; DispWV–dispense water valve; DV–drain valve; EH–evaporator heater; FM–fan motor; GM–gear motor; GMPR–gear motor protect relay; IDM–ice dispensing motor; IDS–ice dispensing shutter solenoid; UFS–upper float switch; WV–inlet water valve

35

Page 35
Image 35
Hoshizaki dcm-75ibah LED Lights and Audible Alarm Safeties, Icemaking Sequence Sequence Step, Energized Components Min Max