HP recommends using cable tie wraps to secure the base station to an available support bracket.

2.Connect the data transfer cable from the HP Plenum Rated Sensor Array to the base station.

3.After all hardware is installed, power up the components ("Power up procedure" on page 70).

Installation is complete.

Single CRAH installation diagram

Callout

Component

Description

 

 

 

1

CRAH return air stream

The return air side of the CRAH

2

CRAH supply air stream

The supply air side of the CRAH

3

Base station

The base station is mounted on the supply air side of the CRAH.

4

Supply side of plenum array

The three-point plenum array that measures the supply air temperature

 

 

and humidity.

5

Return side of plenum array

The three-point plenum array that measures the return air temperature

HP Environmental Base Station installed on a CRAH/CRAC 27