c.Using a flathead screwdriver, secure the black wire to the negative terminal block on the current sensor transducer.

d. Insert the connector from the wire harness into the Current Sensing Relay Base Station.

3.Connect one end of the 24V AC adapter to the power input connector on the base station, and then plug the other end of the AC adapter into a power source. The base station automatically powers up and follows the Base Station LED sequence.

IMPORTANT: Verify that the jumper setting of the CT matches the amperage of the electrical equipment you connect it to.

4.Adjust the jumper setting of the CT to match the amperage of the electrical device. o Low—O-100 amps

o Medium—0-150 amps o High—0-200 amps

Installation is complete.

Installing the HP 200A Current Base Station

The HP 200A Current Base Station connects to the supplied current sensor and measures and reports the current flowing to electrical equipment. The base station provides three channels to monitor three different power line feeds. Consult a professional electrician to install the current sensor to your component.

To install a 200A Current Base Station:

1.Determine the ideal location for the 200A Current Base Station, relative to your current sensor.

(Optional) Sensor Base Stations 51