Recommended base configuration

HP recommends the following base configuration for your data center:

Two Base Station Gateways for every 400 base stations (A minimum of one base station gateway is required per wireless network.)

One Environmental Base Station and Plenum Rated Sensor Array for every CRAH/CRAC

One Environmental Base Station and Rack Sensor Array or Three Point Sensor Array for every three racks

One Air Pressure Base Station for every 50 m2 (500 ft2) of data center floor space

Callout

Component

 

 

1

HP Air Pressure Base Station

2

HP Environmental Base Station

3

HP Base Station Gateway

4

HP Rack Sensor Array

5

HP Plenum Rated Sensor Array

6

HP Three Point Sensor Array

Consult your data center administrator for detailed placement and configuration information.

HP Data Center Environmental Edge hardware overview 5