9.Select the Basic tab, and then select Download to transfer the new settings into the Chilled Water Base Station.

10.Select OK to save the configuration settings and close the System Configuration window.

Testing the configuration

The 4mA and 20mA calibration values are factory set and must not be modified. If you modify these calibration values and select Download, you will override the 4-20mA factory preset.

You can test the analog flow meter output for troubleshooting purposes. The Test field represents the Flow Meter 4-20mA analog output value, but not the flow rate. The minimum value is 4 and the maximum value is 20.

NOTE: Do not select Download during the testing or calibration process.

To test the calibration:

1.Select the Calibration/Test box. The Calibration and Test fields are now active.

2.Using whole numbers, adjust the Test field.

3.Verify the flow rate on the console matches the calibration of your flow rate.

Example:

(Optional) Sensor Base Stations 45