Generator

Generator

 

3.5CFZ

 

5CFZ

Rated kW

3.5

 

5

Frequency--Hz

50

 

50

Rated Voltage

110 Volt, 2&3 Wire, Single Phase or

110/220 Volt, 3 Wire, Single Phase

Rated Amps (110 Volt)

31.8

 

45.5

Rated Amps (220 Volt)

15.9

 

22.7

Rotor Resistance (cold) (ohms)

4--5

 

4--5

Stator Resistance (cold) (ohms)*

 

 

 

Leads:

 

 

 

1--2, 3--4

0.8

 

0.8

55--66

4.2

 

4.2

B1--B2

0.08

 

0.08

 

4CZ

 

6.5CZ

Rated kW

4

 

6.5

Frequency--Hz

60

 

60

Rated Voltage

120 Volt, 2&3 Wire, Single Phase or

120/240 Volt, 3 Wire, Single Phase

Rated Amps (120 Volt)

33.3

 

54.2

Rated Amps (240 Volt)

16.7

 

27.1

Rotor Resistance (cold) (ohms)

3--4

 

4--5

Stator Resistance (cold) (ohms)*

 

 

 

Leads:

 

 

 

1--2, 3--4

0.06

 

0.04

55--66

1.9

 

2.4

B1--B2

0.09

 

0.06

 

3.5CFZ/4CZ

 

5CFZ/6.5CZ

Generator Type

Two-Pole,

Rotating Field

Voltage Regulation

 

±5%

Frequency Regulation

 

±5%

Angular Operation (Max.)

 

20°Continuous

(in all directions)

 

 

 

 

Excitation Method

Brushless, Exciter Winding/Capacitor

Coupling Type

Tapered Shaft--Thru-Bolt

Stator Bolt Torque in. lbs. (Nm)

 

260 (29)

Thru-Bolt Torque ft. lbs. (Nm)

 

37 (50)

Number of Output Leads

 

4, Reconnectable

Insulation (Rotor and Stator)

Class F, Epoxy Varnish, Vacuum Impregnated

Winding Material

 

Copper

Bearing, Number and Type

 

1, Replaceable Ball

Circuit Protection:

 

 

 

Controller

Replaceable 10-Amp Fuse

Battery Charging

Replaceable 10-Amp Fuse

AC Circuit Breakers

 

Optional

* Most ohmmeters will not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with a reading indicating a shorted winding.

1-2 Specifications