isolator or isolation transformer is referenced in ABYC
Generator sets installed in commercial vessels are governed by U.S. Coast Guard Regulations, Title 46, the American Bureau of Shipping, and Lloyd’s Register of Shipping. Grounding of equipment is covered in ABS
35.9.6and Lloyd’s Part 6, Chapter
Battery
Batteries and their installation must conform to U.S.C.G. Regulations 183.420 (a) through (g). Generator sets should use batteries separate from the propulsion engines whenever possible. Both the generator set and the propulsion engines’starting/charging systems must have a common negative
U.S.C.G Regulation 183.415, Grounding, requires a common conductor to be connected to each grounded cranking motor circuit. This conductor should be sized to match the larger of the engines’two battery cables. (Cable sizes for generator set battery connections are given in Figure
|
| Cable |
|
Distance Between |
| Size |
|
At 0°F | (AWG) | At 75°F | |
Generator Set and | At 32°F | ||
Battery |
| (24°C) | |
40 ft. (12.2 m) | 00 | 0 | 1 |
30 ft. (9.1 m) | 0 | 1 | 2 |
25 ft. (7.6 m) | 1 | 2 | 4 |
20 ft. (6.1 m) | 2 | 2 | 6 |
15 ft. (4.6 m) | 2 | 4 | 6 |
10 ft. (3.0 m) | 4 | 6 | 8 |
5 ft. (1.5 m) | 6 | 6 | 8 |
2.5 ft. (0.8 m) | 8 | 8 | 8 |
Figure 6-20. Battery Cable Sizes
1 |
2 |
1. Battery Positive (+) | 2. Battery Negative |
Connection | Connection |
Figure 6-21. Battery Connection Bracket
Wiring
All wiring must be stranded copper. Wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and overcurrent protection (circuit breakers, fuses) must conform to U.S.C.G. Regulations 183.425 through 183.460. Use rubber grommets and cable ties, as necessary, to protect and secure wiring from sharp objects, exhaust system, and any moving parts.
Installation |