Remote Start Switch Connection
Kohler offers several remote panels for connection to the generator set. See Accessories for further detailed description. A wiring harness with a connector keyed to the controller box connector is available to connect these panels to the generator set. The other end of this harness has pigtails which can be used if the installer
elects to use just a
NOTE
If gauges are to be used, there must also be generator set senders. Senders are optional on these generator sets. Gauges and senders are available as service items from an authorized Kohler service dealer/distributor.
Lead Designations
| Pin | Lead | Function |
| Black | Ground | |
| Tan | Water Temp. Ga. | |
| Lt. Blue | Oil Pressure Ga. | |
| Violet | Gen. “ON”(+) | |
| Yellow/Red | Start | |
| Grey/Black | Stop | |
|
|
|
|
|
|
|
|
|
|
| 1 |
J3
1 2 3
4 5 6
2
WT
7
OP
3
4
5
6
NOTE
All wire is 16 gauge. Tape to insulate all unused lead ends.
1.Use Insulink or Solder Connection (Tape to Insulate)
2.Hourmeter
3.“ON”Light
4.Stop
5.Start
6.Rocker Switch
7.Gauges Senders