Lennox International Inc 2P1109, P506052-01 setup guide Installer setup, DEHUMIDIFICATION modes

Models: 2P1109 Touch Screen Programmable Communicating Thermostat P506052-01

1 39
Download 39 pages 10.69 Kb
Page 13
Image 13
Installer setup − Page 8 of 8
HEAT SETPOINT+COOL SETPOINT
2

Installer setup − Page 8 of 8

setup

tests

equipment

HELP

SYSTEM

 

(to adjust a setting, highlight

 

it, then press edit)

 

 

 

 

Equipment Name

 

Current Value:

 

 

Filter 1 Timer

 

(Display Only)

 

 

 

Selection

 

 

 

.

 

 

 

.

 

 

 

(various)

 

 

 

.

 

edit

reset

.

 

 

 

 

Dehumidification

Control Mode

Humidificationback

Control Mode

Figure 16. SYSTEM adjustment screen

HUMIDIFICATION modes

BASIC & PRECISION modes allow user control of RH between

15 and 45%. These conditions must be met for either mode to operate:

Shumidification mode has been enabled, and

Sthe unit is in HEAT mode, and

Shumidification demand exists (24V present at H), and

SBASIC mode also requires heat demand exists (Y for HP heat, or W for gas heat [W may be energized with G de−energized]).

DEW POINT CONTROL

humidification setpoint based on the outdoor temperature and a user−de- fined dew point adjustment setting.

DEHUMIDIFICATION modes

In BASIC mode, dehumidification occurs if these conditions are met and signals are present at specific terminals:

Sdehumidification has been enabled on installer settings, and

Sthe unit is in COOL mode, and

Sdehumidification demand exists (RH above setpoint), and

Scooling demand exists (Y1 energized).

Dehumidification Control Mode

Display Only

HUMIDIFICATION modes Basic

Precision

Humiditrol

cancel

(or Auxiliary

 

Dehumidifier)

 

save

Humidification Control Mode

Display Only

 

Basic

 

Precision

 

Dew Point Control

cancel

save

In PRECISION mode, dehumidification occurs if all BASIC conditions are true, except cooling demand may or may not be present. Maximum overcool from cooling set point is 2ºF.

HUMIDITROL or AUX. DEHUMIDIFIER mode requires:

Soutdoor sensor must be installed and setup

Sdehumidification has been enabled on installer settings, and

Sthe unit is in COOL mode, (or if in AUTO, at least one thermostat cooling call made prior to the dehumidification demand), and

Sa dehumidification demand exists (RH above setpoint), and

Soutdoor temp. below 95°F; indoor temp. above 65°F, and

Sfor HUMIDITROL, Humiditrol comfort adjust parameters as follows:

MAX adj. − Indoor temp > 2°F above heating setpoint

MID adj. − Indoor temp >

Figure 17. Selecting Dehumidification/Humidification mode

MIN adj. − Indoor temp > 2°F below cooling setpoint

Page 13

icomfortt Touch Screen 7−Day Programmable Thermostat

Page 13
Image 13
Lennox International Inc 2P1109, P506052-01 setup guide Installer setup, DEHUMIDIFICATION modes