Wiring Diagrams − Communicating Systems

Wiring Diagrams − Communicating Systems

DAS NOTE − The discharge air sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

icomfortt

 

 

 

 

 

 

 

 

 

 

FURNACE (IFC) OR AIR HANDLER (AHC)

is intended to be mounted downstream

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPTIONAL DIS-

 

 

of the heat exchanger and air condi-

 

 

 

 

 

 

 

CHARGE AIR SEN-

tioning coil. It must be placed in free

 

 

 

 

 

 

 

SOR (SEE DAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

airflow, where other accessories (such

 

 

 

 

NOTE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

as humidifiers, UV lights, etc.) will not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interfere with its accuracy. Wiring dis-

 

OPTIONAL OUT-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tance between the IFC or AHC and the

DOOR AIR SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

discharge air sensor should not exceed

(SEE OAS NOTE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10ft when wired with 18−gauge thermo-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stat wire.

 

 

 

 

 

 

 

icomfortt

 

 

 

 

 

 

OAS NOTE − Wiring distance between

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the IFC or AHC and the outdoor tem-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

perature sensor should not exceed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200ft when wired with 18−gauge ther-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

icomfortt

mostat wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDITIONING OR

 

 

 

 

 

 

 

 

 

RSBus

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT PUMP UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

icomfortt

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

RSBus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum total length of all connections

icomfortt Indoor Furnace or Air Handler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

icomfortt

Outdoor Condensing Unit or Heat Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the RSBus is limited to 1500ft.

 

 

 

 

 

 

 

 

 

Wire gauge of RSBus wire is 18.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

506052−01 11/09