Alarm Codes and Troubleshooting

 

 

 

Alarm ID

Message Name

Action required to Clear/Recover

 

 

 

241

Flame Out of Sequence − Still Present

Shut off gas, check for gas valve leak.

 

 

 

250

Primary Limit Switch Open

Check firing rate on furnace, blockage in heater, and air flow.

 

 

 

252

Discharge Air Temperature High

Check temperature rise, air flow and input rate.

 

 

 

270

Watch Guard − Flame Failure on Ignite

Check for gas flow, ignitor lighting burner, flame sensor current.

 

 

 

271

Watch Guard − Low Pressure Switch Open

Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water

 

 

column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

272

Watch Guard − Low Pressure Switch Open Run

Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-

 

Mode

ating pressure, inspect vent and combustion air inducer for correct operation and restriction. Check inches of

 

 

water column closing pressure of high pressure switch on heat call, measure inches of water column of operat-

 

 

ing pressure, inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

273

Watch Guard − Flame Fail in Run Mode

Check micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.

 

 

Measure voltage of neutral to ground for good unit ground.

 

 

 

274

Watch Guard − Primary Limit Switch Open

Check why limit is tripping, over fired, low air flow.

 

 

 

275

Watch Guard − Flame Out of Sequence. No

Shut off gas, check for gas valve leak.

 

Flame

 

 

 

 

276

Watch Guard − Calibration Failure

Unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.

 

 

 

290

Ignition Circuit Problem

Measure resistance of Hot Surface Ignition ignitor, replace if open or not within specification; otherwise replace

 

 

control.

 

 

 

291

Heat Airflow Restricted Below Min.

Check for dirty filter, unit air flow restriction, blower performance.

 

 

 

292

Indoor Blower Motor Start Problem

Indoor blower motor unable to start (seized bearing, stuck wheel, etc.). Replace motor or wheel if assembly

 

 

does not operate or meet performance.

 

 

 

294

Inducer Motor Over current

Check combustion blower bearings, wiring, amps. Replace if does not operate or meets performance.

 

 

 

295

Indoor Blower Over Temperature

Indoor blower motor over temperature (motor tripped on internal protector). Check motor bearings, amps; re-

 

 

place if necessary.

 

 

 

310

Discharge Air Sensor Problem

Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace sensor

 

 

if necessary.

 

 

 

311

Heat Rate Reduced to Match Airflow

Furnace blower in cutback mode due to restricted airflow. Check filter and ductwork. To clear, replace filter if

 

 

needed or repair/add ductwork.

 

 

 

312

Reduced Airflow − Indoor Blower Cutback

Restricted airflow − Indoor blower is running at a reduced CFM (Cutback Mode − The variable speed motor has

 

 

pre−set speed and torque limiters to protect the motor from damage caused by operating out of its designed

 

 

parameters (0 to 0.8" w.g. total external static pressure). Check filter and ductwork. To clear, replace filter if

 

 

needed or repair/add ductwork.

 

 

 

 

 