Editable Parameters Table (User and Installer)

Parameter Name:

Default

Parameter Value Setting

Increment

 

 

 

 

Installer settings

Time and Date

 

(Time/date elements screen)

 

 

 

 

 

Daylight Saving Time

Enabled

Enabled, Disabled

 

 

 

 

 

Circulate Fan − Percentage of Time ON

35%

15 to 45%

1%

 

 

 

 

Dealer Contact Information – Name

Lennox

(Typewriter input screen)

 

 

 

 

 

Dealer Contact Information – Address

 

(Typewriter input screen)

 

 

 

 

 

Dealer Contact Information – Phone

1−800−9−LENNOX

(Typewriter input screen)

 

 

 

 

 

Dealer Contact Information – Email

 

(Typewriter input screen)

 

 

 

 

 

Dealer Contact Information – Website

www.lennox.com

(Typewriter input screen)

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

Equipment Name

 

(Typewriter input screen)

 

 

 

 

 

Filter 1 Timer Selection

Calendar Time

Calendar Time, Run Time

 

 

 

 

 

Filter 2 Timer Selection

Calendar Time

Calendar Time, Run Time

 

 

 

 

 

Humidifier Pad Timer Selection

Calendar Time

Calendar Time, Run Time

 

 

 

 

 

UV Bulb Timer Selection

Calendar Time

Calendar Time, Run Time

 

 

 

 

 

PureAir Timer Selection

Calendar Time

Calendar Time, Run Time

 

 

 

 

 

Smooth Setback Recovery

Disabled

Enabled, Disabled

 

 

 

 

 

Electric Heat Control Mode

Standard

Standard, Even Heat

 

 

 

 

 

Gas Heat Control Mode

Modulating

Staged, Modulating

 

 

 

 

 

Autochangeover Temp Deadband

5ºF

3 to 9ºF

1ºF

 

 

 

 

Max Heat Setpoint

90ºF

40 to 90ºF

1ºF

 

 

 

 

Min Cool Setpoint

60ºF

60 to 99ºF

1ºF

 

 

 

 

Heat/Cool Stages Locked In

Disabled

Enabled, Disabled

 

 

 

 

 

table continued on next page

Page 25

icomfortt Touch Screen 7−Day Programmable Thermostat

Page 25
Image 25
Lennox International Inc 2P1109 setup guide Editable Parameters Table User and Installer, Installer settings, Table on next