Lennox International Inc 2P1109, P506052-01 setup guide Alarm Codes and Troubleshooting

Models: 2P1109 Touch Screen Programmable Communicating Thermostat P506052-01

1 39
Download 39 pages 10.69 Kb
Page 34
Image 34

 

Alarm Codes and Troubleshooting

 

 

 

Alarm ID

Message Name

Action required to Clear/Recover

 

 

 

313

Indoor/Outdoor Unit Capacity Mismatch

Incorrect indoor/outdoor capacity code selected. Check for proper configuring in installation instructions. Alarm

 

 

is just a warning. The system will operate, but might not meet efficiency and capacity parameters and alarm

 

 

would clear when commissioning is exited.

 

 

 

345

Relay O Failure

O relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

346

HP Jumper not Removed

Configuration jumper(s) not removed on control board cut O−R. Applicable with non communicating outdoor unit

 

 

with communicating indoor system.

 

 

 

347

Relay Y1 Failure

Y1 relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

348

Relay Y2 Failure

Y2 relay / Stage 2 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

349

IFC Error Check Jumper O to R

Configuration link R to O needs to restored Applicable in non communicating mode,

 

 

 

350

Electric Heat not Configured

Heat call with no configured or mis−configured electric heat. Check for proper configuring under Configuring

 

 

Electric Heat Stages in the air handler installation instructions.

 

 

 

351

Electric Heat Stage 1 Problem

Heat section / Stage 1 failed (Pilot relay contacts did not close or the relay coil in the electric heat section did

 

 

not energize).

 

 

 

352

Electric Heat Stage 2 Problem

Heat section / Stage 2 failed (Same as Code 351).

 

 

 

353

Electric Heat Stage 3 Problem

Heat section / Stage 3 failed (Same as Code 351).

 

 

 

354

Electric Heat Stage 4 Problem

Heat section / Stage 4 failed (Same as Code 351).

 

 

 

355

Electric Heat Stage 5 Problem

Heat section / Stage 5 failed (Same as Code 351).

 

 

 

400

LSOM Compressor Internal Overload Tripped

Compressor protector is open. Check for high head pressure, check compressor supply voltage.

 

 

Outdoor unit power disconnect is open.

 

 

Compressor circuit breaker or fuse(s) is open.

 

 

Broken wire or connector is not making contact.

 

 

Low or high pressure switch open if present in the system.

 

 

Compressor contactor has failed to close.

 

 

 

401

LSOM Compressor Long Run Cycle

Compressor ran over 18 hours on one room thermostat demand.

 

 

 

402

LSOM Outdoor Unit System Pressure Trip

Outdoor unit pressure trip. Check dirty coil, fan motor, refrigerant charge.

 

 

 

403

LSOM Compressor Short−Cycling

Compressor short cycling (Running less than 4 minutes).

 

 

 

404

LSOM Compressor Rotor Locked

Check capacitor, wiring, hard−start kit, replace compressor.

 

 

 

405

LSOM Compressor Open Circuit

 

 

 

Check compressor for hot (cool down), check pressures, fan motor etc. Replace compressor if unable to get

406

LSOM Compressor Open Start Circuit

circuit to close and compressor to operate.

 

 

407

LSOM Compressor Open Run Circuit

 

 

 

 

408

LSOM Compressor Contactor Welded

Replace contactor.

 

 

 

409

LSOM Compressor Voltage Low

Check power to unit.

 

 

 

table continued on next page

506052−01 11/09

Page 34

Page 34
Image 34
Lennox International Inc 2P1109, P506052-01 Alarm Codes and Troubleshooting, Indoor/Outdoor Unit Capacity Mismatch