Lincoln Electric GUN Installation, GAS Connection, Connecting GUN Cable to the SP-100

Models: SP-100

1 62
Download 62 pages 13.43 Kb
Page 11
Image 11

INSTALLATION

A-4

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

3.Route the cable under and around the back of the Wire Feed Gearbox (6).

4.For GMAW Only: Refer to Figure A.2. As deliv- ered, the SP-100 is wired for positive polarity. This is the appropriate configuration for the Gas Metal Arc Welding (GMAW) process. To complete instal- lation, use the provided wing nut to connect the work cable’s terminal lug to the negative (–) output terminal (5) located above the Wire Feed Gearbox

(6). Make sure that both wing nuts are tight.

5.For Innershield Only: Refer to Figure A.4. To wire for negative polarity, connect the short cable attached to the connector block (1) to the negative

(–) output terminal (2) and the work cable (3) to the positive (+) terminal (4).

 

FIGURE A.4

4

3

2

1

GUN INSTALLATION

As shipped from the factory, the SP-100 gun is ready to feed 0.023 - 0.025” (0,6 mm) wire. If 0.030” (0,8

mm)wire is to be used install the 0.030” (0.8 mm) contact tip. Refer to the MAINTENANCE section for contact tip installation details.

CONNECTING GUN CABLE TO THE SP-100

1.Refer to Figure A.2. Unplug the machine or turn power switch to the off “O” position.

2.Pass the insulated terminals of the gun trigger con- trol leads, one at a time, through the Gun Cable and Control Lead Access Slot (2) in the case front. The leads are to be routed under the Wire Feed Gearbox (6) and through the Cable Hanger (7) on the inner panel.

3.Insert the connector on the gun conductor cable into the Gun Cable Access Hole (2) in the SP-100 case front. Make sure the connector is all the way in the metal connector block to obtain proper gas flow. Rotate the connector so control leads are on the underside and tighten the Thumbscrew (8) in the connector block.

4.Connect the gun trigger control lead terminals to the two insulated 1/4" (6,4 mm) tab connector bushings located above the “Gun Trigger Connection” decal in the wire feed section (4). Either lead can go to either connector. Form the leads so that they are as close as possible to the inside panel.

CAUTION

If the gun trigger switch being used is other than that supplied with the SP-100, the switch must be a normally open, momentary switch. The terminals of the switch must be insulated from the welding circuit. Malfunction of the SP-100 may result if this switch shorts to the SP-100 welding output circuit or is common to any electrical circuit other than the SP-100 trigger circuit.

GAS CONNECTION

Refer to Figure A.5

When using the GMAW process, a cylinder of carbon dioxide (CO2) or argon-carbon dioxide mixed shielding gas, flow regulator, and an inlet gas hose must be obtained. For more information about selecting gas cylinders for use with the SP-100, refer to the ACCES- SORIES section.

WARNING

CYLINDER may explode if dam- aged. Keep cylinder upright and chained to support

• Keep cylinder away from areas where it may be damaged.

Never lift welder with cylinder attached.

Never allow welding electrode to touch cylinder.

Keep cylinder away from welding or other live electrical circuits.

SP-100

Page 11
Image 11
Lincoln Electric service manual GUN Installation, GAS Connection, Connecting GUN Cable to the SP-100