INSTALLATION

A-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DEVICE USE WITH THE RANGER® 3 PHASE

 

 

 

 

 

 

 

 

 

 

Type

 

Common Electrical Devices

Possible Concerns

 

 

 

 

 

 

 

 

 

 

Resistive

 

Heaters, toasters, incandescent

NONE

 

 

 

 

light bulbs, electric range, hot

 

 

 

 

 

 

 

 

pan, skillet, coffee maker.

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacitive

 

TV sets, radios, microwaves,

Voltage spikes or high voltage

 

 

 

 

appliances with electrical control.

regulation can cause the capaci-

 

 

 

 

 

tative elements to fail. Surge

 

 

 

 

 

protection, transient protection,

 

 

 

 

 

and additional loading is recom-

 

 

 

 

 

mended for 100% fail-safe oper-

 

 

 

 

 

ation. DO NOT RUN THESE

 

 

 

 

 

DEVICES WITHOUT ADDI-

 

 

 

 

 

TIONAL RESISTIVE TYPE

 

 

 

 

 

LOADS.

 

 

 

 

 

 

 

 

 

Inductive

 

Single-phase induction motors,

These devices require large

 

 

 

 

drills, well pumps, grinders, small

current inrush for starting.

 

 

 

 

refrigerators, weed and hedge

Some synchronous motors may

 

 

 

 

trimmers

be frequency sensitive to attain

 

 

 

 

 

maximum output torque, but

 

 

 

 

 

they SHOULD BE SAFE from

 

 

 

 

 

any frequency induced failures.

 

 

 

 

 

 

 

 

Capacitive/Inductive

 

Computers, high resolution TV sets,

An inductive type line condition-

 

 

 

 

complicated electrical equipment.

er along with transient and

 

 

 

 

 

surge protection is required, and

 

 

 

 

 

liabilities still exist. DO NOT

 

 

 

 

 

USE THESE DEVICES WITH A

 

 

 

 

 

RANGER® 3 PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Lincoln Electric Company is not responsible for any damage to electrical components improperly connected to the RANGER® 3 PHASE machine

RANGER® 3 PHASE Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

(Amps)

 

Volts

 

 

(Watts)

 

14 AWG

 

 

12 AWG

 

 

10 AWG

 

 

8 AWG

 

 

6 AWG

 

4 AWG

 

 

 

15

 

120

 

 

1800

 

30

 

 

(9)

 

 

40

 

 

(12)

 

 

75

 

 

(23)

 

 

125

 

 

(38)

 

 

175

 

(53)

 

 

300

 

(91)

 

 

 

20

 

120

 

 

2400

 

 

 

 

 

 

 

30

 

 

(9)

 

 

50

 

 

(15)

 

 

88

 

 

(27)

 

 

138

 

(42)

 

 

225

 

(69)

 

 

 

15

 

240

 

 

3600

 

60

 

 

(18)

 

 

75

 

 

(23)

 

 

150

 

 

(46)

 

 

225

 

 

(69)

 

 

350

 

(107)

 

 

600

 

(183)

 

 

 

20

 

240

 

 

4800

 

 

 

 

 

 

 

60

 

 

(18)

 

 

100

 

 

(30)

 

 

175

 

 

(53)

 

 

275

 

(84)

 

 

450

 

(137)

 

 

 

40

 

240

 

 

9500

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

(15)

 

 

90

 

 

(27)

 

 

150

 

(46)

 

 

225

 

(69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conductor size is based on maximum 2.0% voltage drop.

RANGER® 3 PHASE

Page 18
Image 18
Lincoln Electric SVM207-A Electrical Device USE with the Ranger 3 Phase, Devices Without Addi Tional Resistive Type Loads