TROUBLESHOOTING AND REPAIR

F-16

 

AUXILIARY AND FIELD WINDING TEST (continued)

FIGURE F.3 – RECEPTACLES AND LEADS

120 VAC GFCI RECEPTACLE

120/240 VAC 1 PHASE

480 VAC 3 PHASE

 

 

 

RECEPTACLE

RECEPTACLE

Lead #3

 

 

Z

GND

 

 

 

 

RESET

TEST

 

 

 

Lead #5

 

Lead #6

Lead #3

 

 

 

Y

X

Return to Section TOC

Section TOC

Return to Master TOC

Master TOC

TEST PROCEDURE

WARNING

ELECTRIC SHOCK can kill.

Turn the machine OFF before working on equipment or making the meter connections. Do not touch electrically hot parts.

AUXILIARY WINDINGS

NOTE: The following tests can be made by carefully inserting the meter probes into the receptacles as indicated. If the probes do not make or maintain contact, the measurements can be made on the back of the receptacles or on the appropriate Circuit Breaker. See the Wiring Diagram.

To test the 120 VAC winding:

1.With the Voltmeter set to read AC Volts (use proper scale), place the probes in one of the 120VAC receptacles as shown in Figure F.3.

2.With the Output Control set at ‘10’, Start the engine and let it run in the HIGH idle mode.

To test the 240 VAC winding:

1.With the Voltmeter set to read AC Volts (use proper scale), place the probes in the 240VAC receptacle where shown in Figure F.3.

2.With the Output Control set at ‘10’, Start the engine and let it run in the HIGH idle mode.

3.The voltmeter should read 240 to 264 volts from lead #3 to lead #6.

4.Turn the engine OFF.

To test the 480 VAC 3 Phase winding:

1.With the Output Control set at ‘10’, Start the engine and let it run in the HIGH idle mode.

2.Set the voltmeter to the proper scale and check the voltage readings per the following table:

PROBES

READING

 

 

X to Y

480 to 520 VAC

 

 

Y to Z

480 to 520 VAC

 

 

X to Z

480 to 520 VAC

 

 

Return to

Return to

3.

The voltmeter should read 120 to 132 volts from

3. Turn the engine OFF

 

 

lead #3 to lead #5.

 

4.

Turn the engine OFF.

 

 

RANGER® 3 PHASE