3-15. Selecting A Location And Connecting 3-Phase Input Power

! Do not move or operate unit where it could tip.

5

18 in (457 mm) for airflow

4

6

1

2

Rear Panel

Tools Needed:

3

= GND/PE Earth Ground

8

3

L1

L2 7

L3

Ref. 803 543-D / 803 766-A

!Installation must meet all National and Local Codes - have only qualified persons make this installation.

! Disconnect and lockout/tagout input power before connecting input conductors from unit.

! Always connect green or green/yellow conductor to supply grounding terminal first, and never to a line terminal.

! Warning: This unit is either a 200/230/460 ac input voltage model or 460/575 ac input voltage model. See rating label on unit and check voltage

available at site to be sure it matches the voltage specified on the rating label.

1Rating Label

2Input Power Cord

3Disconnect Device (switch shown in the OFF position)

4Green Or Green/Yellow Grounding Conductor

5Disconnect Device Grounding Terminal

6Input Conductors (L1, L2 And L3)

7Disconnect Device Line Terminals Connect green or green/yellow grounding

conductor to disconnect device grounding terminal first.

Connect input conductors L1, L2, and L3 to disconnect device line terminals.

8 Over-Current Protection

Select type and size of over-current protection using Section 3-13(fused disconnect switch shown).

Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.