3-15. Selecting A Location And Connecting 3-Phase Input Power

Ref. 803 543-D / 803 766-A
!Installation must meet all National and
Local Codes - have only qualified
persons make this installation.
!Disconnect and lockout/tagout input
power before connecting input
conductors from unit.
!Alw ays c onnect gr een or g reen/yel low
conductor t o supply grounding t erminal
first, and never to a line terminal.
!Warning: This unit is either a
200/230/460 a c input voltage model or
460/575 ac input voltage model. See
rating label on unit and check voltage
available at site to be sure it matches
the voltage specified on the rating
label.
1 Rating Label
2 Input Power Cord
3 Disconnect Device (switch shown in
the OFF position)
4 Green Or Green/Yellow Grounding
Conductor
5 Disconnect Device Grounding Terminal
6 Input Conductors (L1, L2 And L3)
7 Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
termin a l first.
Connect input conductors L1, L2, and L3 to
disconnect device line terminals.
8 Over-Current Protection
Select type and size of over-current
protection using Section 3-13 (fused
disconnect switch shown).
Close and secure door on disconnect device.
Remove lockout/tagout device, and place
switch in the On position.
Tools Needed:
2
1
Rear Panel
18 in (457 mm)
for airflow
!Do not move or operate
unit where it could tip.
= GND/PE Earth Ground

3

3
4
5
7
6
8
L1
L2
L3