3-12. Installing Wire Spool and Adjusting Hub Tension

Use compression spring with 8 in (200 mm) spools.

When a slight force is needed to turn spool, tension is set.

Tools Needed:

15/16 in

072573-B

3-13. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda- tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

 

 

60 Hz Single Phase

 

 

60 Hz Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

200

 

230

460

 

575

200

 

230

460

 

575

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

69

 

61

30

 

24

34

 

30

15

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes

 

 

 

 

 

 

 

 

 

 

 

 

Circuit Breaker 1, Time-Delay 2

80

 

70

35

 

25

40

 

35

15

 

10

Normal Operating 3

100

 

90

40

 

35

50

 

45

20

 

15

Min Input Conductor Size In AWG 4

6

 

8

10

 

12

10

 

10

14

 

14

Max Recommended Input Conductor Length In Feet (Meters)

101

 

86

229

 

217

86

 

114

178

 

277

(31)

 

(26)

(70)

 

(66)

(26)

 

(35)

(54)

 

(85)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG 4

8

 

8

10

 

12

10

 

10

14

 

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

NOTICE − This unit is either a 200/230/460 ac input voltage model or 460/575 ac input voltage model. See rating label on unit and check voltage available at site to be sure it matches the voltage specified on the rating label.

OM-1327 Page 19