6-4-1-2. Bake-Out
The
Mode......: Bake−Out
Control TC:>1
Soak Temp.: 600 Soak Time: 01:00:00
Cool Temp.: 200 Cool Rate: 600 _/Hr
The default position of the cursor is next to Control TC. Press the Increase
or Decrease button to select the number of control
thermocouples to be used for the program. Selections are as follows: 1, 1,2, 1,2,3, or 1,2,3,4. TC1 MUST always be a control thermocouple. TC2 thru TC4 can be used for controlling or monitoring. When a thermocouple is selected as control, the LED adjacent to the
Use the Cursor | button to move the cursor to the desired selection (Soak Temperature, Soak Time, Cool Temperature, or Cool Rate), and |
press the Increase
or Decrease button to change the value to the desired setting.
.The minimum and maximum soak temperature settings for
are 0 and 1000 hours. The minimum and maximum cool rates are 10 and 9999 5/hr. When the system is utilizing
Maximum Temperature Message Screen
Cannot enter Run mode
Programmed temperature settings
exceed air cooled limits
(400 _F, 204 _C)
6-4-1-3. PWHT (Post-Weld Heat Treat)
The
PWHT Screen
Mode......: PWHT
Control TC:>1,2
Ramp Temp.: 200 Ramp Rate: 600 _/Hr
Soak Temp.: 400 Soak Time: 01:00:00