SOPEN − no cable or plug in place

ClntFR − This is the coolant flow rate (in GPM) from the cooler on a liquid-cooled system.

ClrSts − This is the status of the cooler. Possible labels:

SOff

SFlowing

The second diagnostic screen is available by again pressing and holding the Run Status

button and pressing the Parameters

button.

kW V HzA

 

 

System Diagnostic Screen

 

 

VLnA−B: 460V

Therm1:

75

 

DIAG2

VLnB−C: 460V

Therm2:

75

Therm5: OPEN

VLnC−A:

460V

Therm3:

75

ClrTmp:

77

VBus:

650V

Therm4: OPEN

RmtFlw:

Off

VLnA-B − This is the phase to phase line voltage between phases A and B.

VLnB-C − This is the phase to phase line voltage between phases B and C.

VLnC-A − This is the phase to phase line voltage between phases C and A.

VBus − This is the DC bus voltage.

Therm1 − This is the temperature of the current source primary heatsink.

Therm2 − This is the temperature of the bridge heatsink.

Therm3 − This the the temperature of the current source secondary heatsink.

Therm4 − Open (not used).

Therm5 − Open (not used).

ClrTmp − This is the temperature of the coolant on a liquid-cooled system.

SOPEN − no cooler is detected.

RmtFlw − This is the status of the relay contacts for remote coolant flow on a liquid-cooled system.

SOFF

SON

.RmtFlw feature is unsupported on the current platform.

OM-222 166 Page 45

Page 51
Image 51