INSTALLATION AND WIRING
2.2.5 Design information
1)For commercial power
When there is a commercial power
2)If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter’s primary circuit and also make up a sequence which will not switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.
3)When the power supply used with the control circuit is different from the one used with the main circuit, make up a circuit which will switch off the main circuit power supply terminals R, S, T<L1, L2, L3 > when the power supply terminals , R1, S1<L11, L21> for the control circuit are switched off.
4)Since the input signals to the control circuit are on a low level, use two parallel micro signal contacts or a twin contact for contact inputs to prevent a contact fault.
5)Do not apply a large voltage to the contact input terminals (e.g. STF) of the control circuit.
6)Do not apply a voltage directly to the alarm output signal terminals (A, B, C). Always apply a voltage to these terminals via a relay coil, lamp, etc.
7)Make sure that the specifications and rating match the system requirements.
1) Commercial power | 2) |
| |||
|
|
| MC1 |
|
|
|
|
| Interlock |
|
|
Power | R, <L1> | U | IM |
|
|
|
|
|
| ||
supply | S, <L2> | V |
|
| |
MC2 |
|
| |||
|
|
| |||
| T, <L3> | W | Sneak current |
|
|
| Inverter |
|
| Twin contact |
17